Style 55011 / 55021 (CG-S)
The luminaires with IP54 are
suitable for increased sealing re-
quirements for indoor rooms and
protected outdoor areas (e.g. under
porches). They are not suitable for
general use in outdoor areas!
PG 11
L(U)
PE
N(0)
Fig. 5
Fig. 6
Fig. 7
10

5. Installation

For the mounting and operation
of electrical apparatus,
the respective national
safety regulations (e. g.
ElexV, equipment safety law for
Germany) as well as the gen
eral rules of engineering will
have to be observed.

5.1 Mounting

After fixing the quick mounting
plate in accordance with the re-
spective instructions, the mains
connection (L (U), N (0), PE) is to
be established (fig. 5). Pay atten-
tion to a tight fit of the terminal
screws! Unused cable entries are
left with their locking plug fitted
(IP protection).
In order to fix the luminaire, the
opening in the body of the lu-
minaire is placed on the guide
pin (fig. 1) of the quick assem-bly
plate. Then all four corners of the
body of the luminaire are pushed
down until they distinctly lock in
on the quick mounting plate (the
snap hooks engage in the quick
mounting plate). When installing
the luminaire with IP 54 protec-
tion, the IP 54 accessories kit is
to be fixed with 4 screws.
Using the pertaining self-
cutting screws 3.5 x 16, the bowl
is evenly screwed down on the
quick mounting set.
Only use handforce to tighten the
screws (max. 0.8 Nm)!
For lamp replacement or ad-
dressing, the snap hooks of the
screen are detached with a slot-
ted screw driver (fig. 6).
In order to detach the body of
luminaire from the quick moun-
ting plate, a slotted screw driver
is inserted into the lateral recess
on the reflector (fig. 7). Through a
slight lateral lever action towards
the outer edge, the snap hook is
released. When slightly pulling
the body of luminaire from the
inside, it disengages from the
quick mounting plate. After ha-
ving released all four snap con-
nections, the body of luminaire
can be removed from the quick
mounting plate; in case of the
IP 54 version the 4 screws will
have to be unscrewed.

5.2 Mounting accessories

Pendulum set
(CEAG No. 400 71 345 972)
Wall bracket
(CEAG No. 400 71 345 974)
Quick mounting plate
(CEAG No. 400 71 345 974)
IP 54 accessories kit
(CEAG No. 400 71345 975)
The attached mounting instruc-
tions have to be observed!
A special version for pendulum
suspension with IP 54 protec-
tion is available under the CEAG
No. 400 71 345 944.
Chain suspension
(CEAG No. 400 71 345 973)
Wire guard
(CEAG No. 400 71 345 911)
5.3. Addressing (only
CG-S luminaires)
Before fitting the screen or
bowl, the addressing of the
individual luminaires will have
to be performed. To do so,
the desired address (1 - 20) is
set on the address switch by
means of a suitable screw dri-
ver (Arrowhead to No., fig. 8).
If the luminaire should not be
monitored the code 0/0 has to
be selected.

Quicklinks ausblenden: