Herunterladen Diese Seite drucken

SLAT AES 28 V Bedienungsanleitung Seite 15

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

1 General information
1.1 Environmental specifications
Operating temperature:
-5 °C to +40 °C at 100 % charge.
-5 °C to +50 °C at 75 % charge.
Storage temperature: -25 to +85 °C.
Relative humidity: 20 to 95 %.
Environment class: 1 (according to EN 12101-10)
1.2 Electrical input and output specifications
1.2.1
Network input
single-phase voltage: 230 Vac (195,5-264,5 Vac).
-
frequency: 50 à 60 Hz (45-65 Hz)
-
class I.
-
neutral systems: TT, TN, IT.
-
Primary current @ 195,5 V
Circuit breaker to be provided upstream: D curve
1.2.2
Output
Rated voltage
Floating voltage set at half-load and at 25 °C.
The AES version can function without load current
The output current In max. can be used on a
single outlet or distributed among all outlets.
Output voltage
Output current In
Maximum specified output current that can be
supplied continuously. (C=battery capacity).
Maximum specified output current greater than I
max a, that can be supplied for a short period of
time during which battery charging is not required.
Current limitation – short circuit current without
battery
Battery charge current
Switching time
The currents (In) shown are at rated output power.
28V/8A 56V/4A
2A
2A
From In to In+15% for output voltage > 50% of Un.
15
28V/8A
24 V
27.2 V
±0.5 %
Imin = 0
In
28V
+/-2%
8A
I max a = In –C/20
I max b = In
Limited to 75 % of In
0s
56V/4A
48 V
54.4 V
±0.5 %
56V
+/-2%
4A

Werbung

loading

Diese Anleitung auch für:

Aes 56 v