3005921-2021-05-25.fm
Setting of MXHP
(Example)
A Cooling start
B Heating start
C
D
E
F
G
H Min. airflow
I
Example 1
3.1.9 MXHP Settings
Start pct.:
Cooling start >
Heating start >
Cooling requirement:
Min. limit >
Max limit >
Heating requirement:
Min. limit >
Max limit >
Dead band OFF:
Min. Voltage
Max Voltage
Min. airflow
Supply airflow >
Confirm setup: >
Menu line
Minimum cooling requirement
before MXHP starts up
Minimum heating requirement
before MXHP starts up
Voltage setting for minimum
Min. limit
cooling power
Voltage setting for maximum
Max. limit
cooling power
Voltage setting for minimum
Min. limit
heating power
Voltage setting for maximum
Max. limit
heating power
Dead band
Voltage range in which
OFF:
associated DX unit is turned off
Minimum airflow requirement
before MXHP starts up
Confirm
Confirm that all settings in this
setup:
menu are correct
Example 2
3.1.9 MXHP Settings
Start pct.:
10.0
%
Cooling start >
10.0
%
Heating start >
Cooling requirement:
1.2
V
Min. limit >
4.9
V
Max limit >
Heating requirement:
5.0
V
Min. limit >
10.0
V
Max limit >
Dead band OFF:
0.0
V
Min. Voltage
1.1
V
Max Voltage
Min. airflow
100
l/s
Supply airflow >
Yes
Confirm setup: >
Function
9/78
8.0
%
8.0
%
0.0
V
4.0
V
0.0
V
10.0
V
0.0
V
0.0
V
200
l/s
Yes
Example 1
Example 2
10%
8%
10%
8%
1,2V
0V
4,9V
4V
5,0V
0V
10V
10V
0-1,1V
Not active
100 l/s
200 l/s
Yes (required)
Yes (required)