Output Calibration
1. Measure the output current.
2. Select 'Calibrate output' from the 'Device' menu.
. Enter the calibration password.
. The  mA adjustment window will open. Adjust the output to
.00 mA using the buttons shown.
Note: you can use PgUp and PgDn controls on the keyboard for
fine adjustment and <CNTRL> + PgUp and <CNTRL> + PgDn for
coarse adjustment.
5. Press Next when the output has settled at .00 mA.
6. Repeat the procedure for the 20.00 mA adjustment.
7. Press OK to save the changes to the instrument.
This completes the output calibration.