Receiving devices are placed in series with the ITXPlus and introduce
additional load resistances into the loop. The total loop load for a
-20 mA loop powered by supply voltage V
So, for example, a ITXPlus powered from a 2 V DC supply can drive a
700 Ω loop load.
PC
ITXPlus block diagram showing CBX100 and PC connection for Setup
All manuals and user guides at all-guides.com
1
2
3
4
is R
s
loop
ITXPlus
Output
Input
CBX100
= 50 x (V
-10).