Warning
Dangerous mains voltage!
After opening the housing, certain parts of this device that may be under dangerous mains voltage
become accessible. Failure to observe these warnings may result in personal injury and damage to
property!
• Only qualified electricians may carry out work on the device in compliance with the electrical
engineering regulations in accordance with the type of use.
• Disconnect the device from the mains before carrying out any work on WTX568..!
• The unit is not equipped with a disconnecting device. An easily accessible bipolar (L,N) isolating
device with a contact gap of at least 3 mm must be provided outside the device in the electrical
system of the building. The disconnect device must be easily accessible to the service technician.
• The specialist staff must be familiar with all the sources of hazard and maintenance measures in
accordance with the regulations specified in these instructions.
1. Push the cable through the enclosed union nut.
2. Feed the cable through the cable gland that is already mounted on the WTX568...
3. Clamp the cable wires.
65 mm
A
(A) Cable type NYM-J3 x 1,5 mm
4. Screw the union nut to the cable gland.
5. Close the power supply compartment.
19.04.2022
B
6 mm
N PE L
2
(B) Mains connection
Mounting | EN
102