Environmental conditions
Compensated temperature range
Operating temperature range
Storage temperature range
Fluid temperature range
mark
4)
mark
Vibration resistance acc. to
DIN EN 68-2-6 at 10 .. 500 Hz
Shock resistance acc. to
DIN EN 60068-2-27
Protection type acc. to DIN EN 60529
Other data
Supply voltage
when applied acc. to UL specification
Residual ripple of supply voltage
Current consumption
Life expectancy
Weight
Smart functions
Operating data logging
(resettable as well as persistent over
the whole life cycle)
Measuring channel-related events
Communication
Note: Reverse polarity protection of the supply voltage, excess voltage, override and short circuit protection
are provided.
FS (Full Scale) = relative to complete measuring range;
1)
The accuracy indications relate to the pressure (process value or ISDU Index 112, Subindex 1
2)
Including non-linearity, hysteresis and repeatability
3)
Standard up to -25 °C with FKM seal, -40 C on request;
4)
Environmental conditions acc. to 1.4.2 UL 61010-1; C22.2 no. 61010-1. (For HPT 1000S the extension
of the certificate is in process.)
5)
with mounted mating connector in corresponding protection type, the torque value may not
be exceeded.
Contact
Enquiries for products & documents
HYDAC ELECTRONIC GMBH
Hauptstr. 27
D-66128 Saarbrücken
Germany
Web:
www.hydac.com
E-Mail:
electronic@hydac.com
Phone:
+49 (0)6897 509-01
Fax.:
+49 (0)6897 509-1726
-25 .. +85 °C
-40 .. +100 °C / -25 .. +100 °C
-40 .. +100 °C
3)
-40 .. +125 °C / -25 .. 125 °C
EN 61000-6-1 / -2 / -3 / -4
Certificate No.: E318391 (for HPT 1000)
 25 g
100 g / 6 ms / half-sine
500 g / 1 ms / half-sine
5)
IP 67
9 .. 35 V DC (18 .. 30 V DC for communication operation)
- limited energy – acc. to 9.3 UL 61010; Class 2;
UL 1310/1585; LPS UL 60950
≤ 5 %
< 25 mA (without communication)
>10 million load cycles (0 .. 100 % FS)
~ 45 g
Only for HPT 1000S
Pressure (Min / max / average value) Operating time
e.g. general (hour counter); Arrhenius value (device temp.
weighted operating time)
General measuring channel-related operating times
Event counter; Statistics for the actual use (operation per
measuring range segment / over / undershooting, overload
etc.)
Via IO-Link
Enquiries about repairs & service
HYDAC SYSTEMS & SERVICES GMBH
Hauptstr. 27
D-66128 Saarbrücken
Germany
Phone: +49 (0)6897 509-1936
Fax.:
+49 (0)6897 509-1933

Werbung