Herunterladen Inhalt Inhalt Diese Seite drucken

Refrigerant Piping - Hitachi Rpim-0.8Fsn2E Installationsanleitung

Vorschau ausblenden Andere Handbücher für RPIM-0.8FSN2E:
Inhaltsverzeichnis
Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 27

3. REFRIGERANT PIPING

3.1. PIPING CONNECTION
Access to the refrigerant Pipes connections by removing the
Fan cover from the unit.
The location of refrigerant pipes connection is the following:
(Detail of A)
Gas Piping
Liquid Piping
Liquid Piping
Gas Piping
REFRIGERANT PIPING
Size of piping connection
Model RPIM
Pipe size
Gas Piping
Ø 12.7 (1/2")
Liquid Piping
Ø 6.35 (1/4")
Flare Pipe Dimensions
Nominal
d
A
Diameters
1/4"
6.35
3/8"
9.53
1/2"
12.7
5/8"
15.88
Flare Nut Dimensions
Nominal
Outer
Diameters
Diameters
1/4"
6.35
3/8"
9.53
1/2"
12.70
5/8"
15.88
Thickness of Copper Pipes
Nominal
Outer Diameters
Diameters
1/4"
6.35
3/8"
9.53
1/2"
12.7
5/8"
15.88
3
5
(mm)
(mm)
+0/-0.4
9.1
13.2
16.6
19.7
(mm)
B
17
22
26
29
(mm)
Thickness
0.80
0.80
0.80
1.00
Inhaltsverzeichnis
loading

Inhaltsverzeichnis