8. TECHNICAL SPECIFICATIONS
Quattro
PowerControl / PowerAssist
Integrated Transfer switch
AC inputs (2x)
Maximum feed through current (A)
Minimum PowerAssist current (A)
INVERTER
Input voltage range (V DC)
Output
(1)
Cont. output power at 25°C (VA)
Cont. output power at 25°C (W)
Cont. output power at 40°C (W)
Cont. output power at 65°C (W)
Peak power (W)
Maximum efficiency (%)
Zero-load power (W)
Zero-load power in AES mode (W)
Zero-load power in Search mode (W)
CHARGER
Charge voltage 'absorption' (V DC)
Charge voltage 'float' (V DC)
Storage mode (V DC)
Charge current house battery (A)
Charge current starter battery (A)
Battery temperature sensor
GENERAL
Auxiliary AC output
Programmable relay
(5)
Protection
(2)
Common Characteristics
ENCLOSURE
Common Characteristics
Battery-connection
230 V AC-connection
Weight (kg)
Dimensions (hxwxd in mm)
STANDARDS
Safety
Emission / Immunity
1) Can be adjusted to 60Hz and to 240V
2) Protection
a. Output short circuit
b. Overload
c. Battery voltage too high
d. Battery voltage too low
e. Temperature too high
f. 230VAC on inverter output
g. Input voltage ripple too high
24
12/3000/120-50/50
230V
Input voltage range: 187-265 VAC
9,5 – 17
Output voltage: 230 VAC ± 2%
3000
(3)
2400
2200
1700
6000
93
20
15
8
14,4
13,8
13,2
120
(4)
Operating temp.: -40 to +65°C (fan assisted cooling)
Material & Colour: aluminium (blue RAL 5012)
24/3000/70-50/50
230V
Yes
Yes
Input frequency: 45 – 65 Hz
AC-in-1: 50A
AC-in-2: 50A
AC-in-1: 5,3A
AC-in-2: 5,3A
19 – 33
Frequency
3000
2400
2200
1700
6000
94
20
15
10
28,8
27,6
26,4
70
4
yes
Max load: 25A Switches off when in inverter mode
Yes
a - g
Four M8 bolts (2 plus and 2 minus connections)
Screw terminals 13mm² (6 AWG)
19
362 x 258 x 218
EN 60335-1, EN 60335-2-29
EN 55014-1, EN 55014-2, EN 61000-3-3
3) Non-linear load, crest factor 3:1
4) At 25°C ambient
5) Programmable relay which can be set for general
alarm, DC undervoltage or genset start/stop function
AC rating: 230V/4A
DC rating: 4A up to 35VDC and 1A upto 60VDC
48/3000/35-50/50
230V
Power factor: 1
38 – 66
50 Hz ± 0,1%
:
3000
2400
2200
1700
6000
95
25
20
12
57,6
55,2
52,8
35
Humidity (non condensing): max 95%
Protection: IP 21

Werbung

loading

Diese Anleitung auch für:

Quattro 24/3000/70-50/50 230vQuattro 48/3000/35-50/50 230vQuattro 12/3000/120-50/50-230v