RMH 0002 A
Functional description
d 2 Circuit form-C relay module with feedback.
Each output is equipped with normally opened (NO) and normally closed (NC) contact.
The outputs are not supervised!
Wiring
Pos.
Marking
1
NC1
2
C1
3
NO1
10
NC2
11
C2
12
NO2
15
FB1 +
16
FB1 -
21
FB2 +
22
FB2 -
RISK OF ELECTRIC SHOCK !
Danger of life with contact of live parts and wires.
DANGER
" Disconnect power before connecting equipment!
Technical Specification
Indication/operation elements
Input voltage (min - max)
Feedback current
Feedback output voltage
Maximum current consumption
- standby mode
- with both relays actuated
Max. relay contact rating
Fuses
Operating temperature
Storage temperature
Permissible relative humidity
Housing material and color
Dimensions (H x W x D)
Weight
Bosch Sicherheitssysteme GmbH
Connection
Zone 1 relay
Zone 2 relay
Feedback zone 1
Feedback zone 2
4 LEDs (2x red, 2x green) / 2 Keys (LED test)
20 V DC - 30 V DC
Maximum 8.5 mA per zone
Maximum 30 V DC
13.5 mA
53.5 mA
5 A at 120 V/230 V AC or 5 A at 30 V DC
F1 = T 6.3 A, F2 = T 6.3 A
-5 _C . . . 50 _C
-20 _C . . . 60 _C
max. 95%
ABS plastic Cycolac VW300 (UL94 5VA),
semi-gloss anthracite, RAL 7016
approx. 127 x 96 x 60 mm (5.0 x 3.8 x 2.4 inches)
approx. 135 g (4.8 ounces)
1
15
(23 _F . . . 122 _F)
(-4 _F . . . 140 _F)
en | 10
2 3
10 11 12
16
21
22
4.998.153.981 | 4.0 | 2009.04

Werbung

loading

Diese Anleitung auch für:

4.998.137.274