Herunterladen Diese Seite drucken

IFM Electronic ClassicLine AC5222 Montageanleitung Seite 9

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Parameter setting of the analogue module
Parameter bit/
Designation
P0
filter
P1
channel 2
P2
peripheral fault
P3
not used
Electrical connection
Connect the plugs of the sensors / actuators to the M12 sockets.
To guarantee the protection rating IP 67
• cover the unused sockets with protective caps (E73004)*, tightening
torque 0.6...0.8 Nm
• use the flat cable end seal (E70413)* if the module is at the end
of the cable line.
* to be ordered separately
The earthing lead (2.8 x 0.5 mm) on the supplied lower part is connec-
ted to pin 5, functional earth of the M12 sockets.
Description
1*
50Hz filter in the A/D
converter active
0
60Hz filter in the A/D
converter active
1
channel 2
enabled
channel 2
0
not enabled
1
peripheral fault active
0
peripheral fault not active
1
reserved
0
reserved
Remarks
The 50Hz filter applies
to the whole of Europe
The projection has an effect on the con-
version time in the AS-i slave, the trans-
mission via the AS-interface, the LED
function and on the peripheral fault mes-
sages. The LED indication and peripheral
fault messages are no longer affected by
this channel. By disabling channel 2 the
conversion time in the slave can be
reduced considerably.
* default setting
9

Werbung

loading