Herunterladen Diese Seite drucken

Eaton CROUSE-HINDS-Serie Betriebsanleitung Seite 7

Explosionsgeschützte steckvorrichtung 63 a, 4- und 5-polig
Vorschau ausblenden Andere Handbücher für CROUSE-HINDS-Serie:

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Code Zone 1
3-pol. + PE
3-pol. + N + PE
Wall socket,
4- and 5-pole
Plug,
4- and 5-pole
Dimensions in mm
X = fixing dimensions
Explosion-protected plugs and sockets
63 A, GHG 514
1
Technical data
1.1
Plug and socket GHG 514
EU-Type Examination Certificate:
(special conditions see
X
)
ATEX - IEC
Marking acc. to 2014/34/EU
and standard of series EN 60079: gas
IECEx Certificate of Conformity:
(special conditions see
X
)
ATEX - IEC
Category of application
standard of series IEC 60079:
Rated voltage:
Rated current:
Back-up fuse:
without thermal protection
with thermal protection
Switching capacity AC 3:
Perm. ambient temperature:
(1)
Install protected against higher mechanical risk. Wall sockets with external earth pin only -40 °C.
X
ATEX - IEC
(Special versions permit deviating temperatures.)
Perm. storage temperature in original packing:
**Protection category acc. to IEC/EN 60529
with closed and secured hinged cover as well
as combinations properly plugged together
Insulation class acc. to IEC/EN 61140:
Cable entry:
wall socket
suitable cables and test torques of the
pressure screw
Seal 1+2+3
1 2
3
Seal 1+2
1 2
3
Seal 1
1 2
3
Test torque for screw in thread cable entry (Nm)
(2) The tests of clamping ranges and torque values were performed with metal mandrel. The clamping range can vary by using
cables with different manufacturing tolerances and material properties. Please use a suitable combination of seals in the
intermediate area, so that the cap nut can be tightened in future maintenance work on the cable entry.
Possible cable glands (KLEs) (special versions)
KLEs made of plastic:
KLEs made of metal:
Plug
Supply terminal:
wall socket
plug
Test torques:
Cover screws
Terminals, plug
Terminals, wall socket
Self-cutting screws size 4
Self-cutting screws size 5
Self-cutting screws size 8
Weight:
wall socket
4-pole
GHG 514 44
plug
4-pole
GHG 514 74
wall socket
5-pole
GHG 514 45
plug
5-pole
GHG 514 75
Auxiliary contact:
Rated voltage:
Rated current:
Switching capacity:
BVS 17 ATEX E 073 X
II 2 G Ex db eb IIC/IIB T5 Gb
dust
II 2 D Ex tb IIIC T80 °C Db
IECEx BVS 17 .0062 X
gas
Ex db eb IIC/IIB T5 Gb
dust
Ex tb IIIC T80 °C Db
up to 690 V, 50/60 Hz
max. 63 A
max. 63 A
max. 80 A gG
up to 690 V / 63 A
(1)
IIB
4 J
/ 7 J -55 °C / -40 °C ... +55 °C
IIC
-20 °C ... +55°C
-55 °C ... +55 °C
IP 66 (catalogue version)
I - is complied with by the devices
(catalogue version)
1x M50 + 1x blanking plug M50
Ø
--
min.
max. (2)
min.
24.0
max. (2)
28.0
min.
28.0
max. (2)
35.0
7.5
M16 x 1,5 ... M63 x 1,5
M16 x 1,5 ... M50 x 1,5
Ø 19 - 34 mm
Cross section
2 x 4 - 25 mm²
(with cable lugs 1 x 35 mm²)
1 x 4 - 16 mm²
(with cable lugs 1 x 25 mm²)
2.50 Nm
2.40 Nm
3.50 Nm
2.00 Nm (Page 10, Pos.10)
3.00 Nm (Page 10, Pos.5)
3.50 Nm
(catalogue version)
approx. 8.10 kg
approx. 0.75 kg
approx. 8.15 kg
approx. 0.80 kg
690 V AC
20 A
AC 15
400 V / 6 A
DC 13
24 V / 2 A
GB
Nm
--
6.0
7.0
5.0
7.0
Stripped wire length
19 mm
12 mm
7

Werbung

loading

Diese Anleitung auch für:

Crouse-hinds ghg 514