Greenlee 560XL Bedienungsanleitung Seite 29

Vorschau ausblenden Andere Handbücher für 560XL:

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

560XL • 567XL • 568XL • 570XL • 573XL • 577XL • 578XL • 580XL
Dual-Wavelength SM Loss Measurements (cont'd)
5. Connect the dual laser source and optical power meter to opposite
ends of the link under test. Use suitable reference cables to connect the
instruments to the patch panel. See figure below.
6. Set the dual laser source to 1310 nm and the optical power meter to
1310 nm. Record the dB reading on the optical power meter. This is the
link loss at 1310 nm.
7. Now set the dual laser source and optical power meter to 1550 nm.
Record the dB reading on the optical power meter. This is the link loss
at 1550 nm.
8. Go to the next fiber and repeat from Step 1.
A
Test
jumper 1
Source
SM cable
plant
Test
jumper 2
Power meter
B
29