4.
PNEUMATIC CONNECTION
The air flow is from port 1 to port 2.
Exhaust
Pressure supply
Inch screw connections (pipe threads) must be used.
Each screw connections must be lined with a fitting synthetic sealing disc.
Do not use Teflon sealing tape or hemp as they may get inside the valve and damage it.
Use an appropriate silencer at port (3). The exhaust time may vary depending on the type of silencer used.
The diameter of the pneumatic lines must be adjusted to the nominal diameter of the valve. The diameter of outlet
line (2) must be larger or equal to that of inlet line (1).
The supply pressure must always be less than the value given in the table in section 3 and must always be above
the desired outlet pressure.
5.
TECHNICAL CHARACTERISTICS
CONSTRUCTION
Directly operated valve
Body: Aluminium
Internal parts: POM
Seals: Nitrile (NBR), fluorelastomer (FPM)
Degree of protection: IP65
Safety code:
q
q
5.1
FLUID CHARACTERISTICS
FLUIDS
PORTS
MAX. INLET PRESSURE
TEMPERATURE / FLUID
TEMPERATURE / AMBIENT
HYSTERESIS
LINEARITY
REPEATABILITY
MINIMUM SETPOINT
MINIMUM OUTLET PRESSURE
8
3
1
II 3D Ex tc IIIC T135°C Dc X
II 3G EX ec IIC T4 Gc X
0 ≤ Ta ≤ +50°C
: Air or neutral gases, filtered at 50 µm, condensate-free, lubricated or
unlubricated
Class 5 according to ISO 8573-1:2010 [7:4:4]
: G1/8-G1/4-G1/2-G1
: see section 1.1
: 0...60 °C
: 0...50 °C
: <1% of span
: <0,5% of span
: <0,5% of span
: 50mV (0,1 mA/4,08mA) with shut-off function
: 1% of span
Visit our website at Emerson.com/AVENTICS
INSTALLATION
Assembly position: any; for optimum performance
vertically with solenoid at the top.
Connections: without hemp or Teflon sealing tape
Electrical connection: Select a wire section that will
give a a voltage drop of less than 2 volts at 2A.
INSTALLATION
2
Pressure outlet