3 Commissioning
28
Commuwin II operating matrix
Fig. 3-3: Commuwin II operating matrix:
A = Unit functions only active on customer specific linearisation
B = Unit functions only active on TC connection
C = Unit functions only acitve on RTD 2 wire connection.
3.2.4 Configuration using HART
software ReadWin
The configuration of the transmitter can be done using both the HART
®
ReadWin
2000 configuration software. The following table shows the structure of the
interactive menu led operation of READWIN
Configurable parameters (Unit function description see "Description of unit functions" on page 29)
Standard settings
Expanded settings
Service functions
®
protocol and PC configuration
®
2000
®
2000.
– Type of sensor
– Connection mode (2-,3-, or 4-wire connection on RTD)
– Units (°C, °F or K)
– Measurement range start value
– Measurement range end value
– Coefficient X0 to X4 (on sensor type polynom RTD/TC)
– Temp.-compensation (on sensor type polynom TC)
– Cold junction compensation internal/external (on TC)
– Temperature external (on TC with cold junction compensation
external)
– Cable resistance compensation (on RTD 2-wire connection)
– Fault condition reaction
– Output (4 to 20 mA/20 to 4 mA)
– Damping (filter)
– Offset
– TAG (Measurement point description)
– Identifier (Descriptor)
– Simulation (on/off)
– Reset/factory default
– Series number (only display)
– Operation code (=release code 281)