70°: Rotate the adapter (Figure 2 e.) in the same manner as
before to the 70° position. Slightly loosen the Phillips screw in
the cam wheel b. so that the wheel can be moved by hand.
Rotate the cam wheel b. clockwise until the switch button
can be seen. Then tighten-back the Phillips screw in the cam
wheel b..
Ordering Codes
Codes
Descriptions
M9132-AGA-1N
Actuator AC/DC 24 V
M9132-AGC-1N
Actuator AC/DC 24 V with 2 auxiliary switches
M9132-AGx-1N
Actuator AC/DC 24 V with feedback potentiometer
M9132-ADA-1N
Actuator AC 230 V
M9132-ADC-1N
Actuator AC 230 V with 2 auxiliary switches
M9132-ADx-1N
Actuator AC 230 V with feedback potentiometer
Technical Specifications
Actuators
Drive torque
Damper area
Running time
Power supply
Frequency
Power consumption:
- operating
- at end stops
For wire sizing
Weight
Control signals
Position indication
Angle of rotation:
- Working range 90° (93° mech.)
Auxiliary switch rating
Sound power level
Protection class
Degree of protection
Temperature: operating/store
Humidity
Maintenance
Conformity
Indipendent of load, at nominal conditions and room temperature
AC 24 V ±20% / DC ±10%
3.0 VA / 3.4 A @ 2ms
ON/OFF and Floating
Mechanical / Potentiometer
- Limiting 5°...85° in 5° steps
3 (1.5) A, AC 230 V
45 dB (A)
II
IP 54 (with cable glands, cable downwards)
-20°...+50 °C / -30°...+60 °C
5...95% RH (not condensing).
Maintenance-free
EMC Directive 2004/108/EC:
EN 55011:2007
EN 55022:2006 A1:2007
EN 61000-3-2:2006
EN 61000-3-3:2008
EN 61000-4-2:2001
EN 61000-4-3:2006
EN 61000-4-4:2007
EN 61000-4-5:2006
EN 61000-4-6:2007
EN 61000-4-8 :1994 A1:2001
EN 61000-4-11:2004
EN 61000-6-1:2007
EN 61000-6-3:2007
IS_M9132-AGx-1N / M9132-ADx-1N_14-88360-1963_Rev. B_12 2009
Factory setting of auxiliary switches
The two auxiliary switches a. and b. are factory set at the to
approximately 10° CW (a.) and 80° CW (b.).
M9132-AGx-1N
32 Nm
2
6 m
140 s
50-60 Hz
4.0 W
0.5 W
1.1 kg
This document is subject to change without notice
M9132-ADx-1N
32 Nm
2
6 m
140 s
AC 230 V ±15%
50-60 Hz
5.5 W
1.0 W
4.5 VA / 0.25 A @ 2ms
1.2 kg
Low Voltage Directive 2006/95/EC:
EN 60730-1A:2002
EN 60730-2-14:2002
2