Verfügbare Sprachen

Max. operating temperature in
b45
heating
Min. operating temperature in
b46
heating
Quantity of machines work in
b55
series
b56 Display machine work in series
b60 Manual debugging mode
PLEASE NOTE. Parameters not listed in the table are not used for the management of this model.

10.4 ECO MODE - Heating curve

In ECO Mode, the unit runs according to heating curve. The heating curve is the relationship between the heating
system supply temperature and the outside air temperature. In the case of a heating curve, it is done automatically
thanks to the weather-based control, which adjusts the supply temperature based on the outside temperature.
Press simultaneously
setting/setting of parameters. b17, b18 and b19 as in the list above.
The heating curve parameters setting is only for technician operation.
a. In main menu, press
set parameters. Press
b. In parameter setting menu, if there is no operation for 30 seconds, will automatically exit parameter setting and
back to main menu. Or press
Description
b17
Set room temp
b18
Initial BTW temp
b19
Max. BTW temp
Target Buffer Tank Water temp = Initial BTW temp + (Max BTW temp - Initial BTW temp) / 35 x (Set room temp -
96
,
and
,
button for 3 seconds to enter parameter setting menu, press
button to save setting.
button to back to main menu.
55
°C
10~60
-25
°C
-35~10
1
1
0
buttons simultaneously to enter / exit ECO mode, the
Default value
Unit
25
20
43
 
1~8
1~8
0: off
0~1
1: on
or
Range
°C
15~25°C
°C
15~25°C
°C
24~50°C