Herunterladen Inhalt Inhalt Diese Seite drucken

Securing Installation And Service Space; Indoor Unit Accessories; Fixing Hanging Bolts; Installing The Unit - Mitsubishi Electric Mr.Slim PEAD-M35JA2 Installationshandbuch

Vorschau ausblenden Andere Handbücher für Mr.Slim PEAD-M35JA2:
Inhaltsverzeichnis

Werbung

3. Selecting an installation site & Accessories

3.2. Securing installation and service space

• Select the optimum direction of supply airflow according to the configuration of the
room and the installation position.
• As the piping and wiring are connected at the bottom and side surfaces, and the
maintenance is made at the same surfaces, allow a proper space properly. For the
efficient suspension work and safety, provide a space as much as possible.

4. Fixing hanging bolts

4.1. Fixing hanging bolts
[Fig. 4-1] (P. 3)
A Center of gravity
(Give site of suspension strong structure.)
Hanging structure
• Ceiling: The ceiling structure varies from building to one another. For detailed
information, consult your construction company.
Center of gravity and Product Weight
Model name
PEAD-(S)M35JA(L)(2)
PEAD-(S)M50JA(L)(2)
PEAD-(S)M60JA(L)(2)
PEAD-(S)M71JA(L)(2)
PEAD-(S)M100JA(L)(2)
PEAD-(S)M125JA(L)(2)
PEAD-(S)M140JA(L)(2)
The values in the parenthesis are for the PEAD-(S)M·JAL(2) model.

5. Installing the unit

5.1. Hanging the unit body

 Bring the indoor unit to an installation site as it is packed.
 To hang the indoor unit, use a lifting machine to lift and pass through the
hanging bolts.
[Fig. 5-1-1] (P. 3)
A Unit body
B Lifting machine
[Fig. 5-1-2] (P. 3)
C Nuts (field supply)
D Washers (accessory)
E M10 hanging bolt (field supply)

6. Refrigerant piping work

6.1. Refrigerant pipe

[Fig. 6-1] (P. 4)
a Indoor unit
b Outdoor unit
Refer to the Instruction Manual that came with the outdoor unit for the restrictions on
the height difference between units and for the amount of additional refrigerant
charge.
Avoid the following places for installation where air conditioner trouble is liable to
occur.
• Where there is too much oil such as for machine or cooking.
• Salty environment as seaside areas.
• Hot-spring areas.
• Where sulfide gas exists.
• Other special atmospheric areas.
• This unit has flared connections on both indoor and outdoor sides. [Fig. 6-1]
• Insulate both refrigerant and drainage piping completely to prevent condensation.

3.3. Indoor unit accessories

The unit is provided with the following accessories:
No.
a
b
c
d
e
The values in the parenthesis are for the PEAD-(S)M·JAL(2) model.
• If necessary, reinforce the hanging bolts with anti-quake supporting members as
countermeasures against earthquakes.
* Use M10 for hanging bolts and anti-quake supporting members (field supply).
a Reinforcing the ceiling with additional members (edge beam, etc.) must be
required to keep the ceiling at level and to prevent the ceiling from vibrations.
b Cut and remove the ceiling members.
c Reinforce the ceiling members, and add other members for fixing the ceiling
boards.
W (mm)
L (mm)
X (mm)
643
954
340
643
954
340
643
1154
325
643
1154
325
643
1454
330
643
1454
330
643
1654
332
5.2. Confirming the unit's position and fixing hanging
 Ensure that the hanging bolt nuts are tightened to fix the hanging bolts.
 To ensure that drain is discharged, be sure to hang the unit at level using a
level.
Caution:
Install the unit in horizontal position. If the side with drain port is installed
higher, water leakage may be caused.
Piping preparation
• Refrigerant pipes of 3, 5, 7, 10 and 15 m are available as optional items.
(1) Table below shows the specifications of pipes commercially available.
Model
PEAD-
(S)M35
PEAD-
(S)M50
PEAD-
(S)M60
PEAD-
(S)M71
PEAD-
(S)M100
PEAD-
(S)M125
PEAD-
(S)M140
(2) Ensure that the 2 refrigerant pipes are well insulated to prevent condensation.
(3) Refrigerant pipe bending radius must be 10 cm or more.
Name
Pipe cover (for refrigerant piping joint) Small diameter
Pipe cover (for refrigerant piping joint) Large diameter
Bands for temporary tightening of pipe cover and drain socket
Washer
Drain socket
Y (mm)
Z (mm)
375
130
375
130
525
130
525
130
675
130
675
130
725
130
bolts
Outside diameter
Pipe
mm
inch
For liquid
6.35
1/4
For gas
12.7
1/2
For liquid
6.35
1/4
For gas
12.7
1/2
For liquid
9.52
3/8
For gas
15.88
5/8
For liquid
9.52
3/8
For gas
15.88
5/8
For liquid
9.52
3/8
For gas
15.88
5/8
For liquid
9.52
3/8
For gas
15.88
5/8
For liquid
9.52
3/8
For gas
15.88
5/8
Quantity
1
1
8(7)
8
1
Product Weight (kg)
25.0 (24.5)
26.5 (25.5)
29.5 (29.0)
29.5 (29.0)
37 (36)
38 (37)
42 (41)
Min. wall
Insulation
Insulation
thickness
thickness
material
0.8 mm
8 mm
0.8 mm
8 mm
0.8 mm
8 mm
0.8 mm
8 mm
0.8 mm
8 mm
1.0 mm
8 mm
Heat resisting
0.8 mm
8 mm
foam plastic
0.045 specific
1.0 mm
8 mm
gravity
0.8 mm
8 mm
1.0 mm
8 mm
0.8 mm
8 mm
1.0 mm
8 mm
0.8 mm
8 mm
1.0 mm
8 mm
15

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis