ELECTRICAL WIRING DIAGRAM

Electrical connection thermostat
N
M
1
2
3

MENU FUNCTIONS

The service menu of the room thermostat RT 10 contains advanced settings that change its operation.
Hold down the keys
Name
Description of the functions
SEN
Sensor functions
OSV
Floor temperature limitation
DIF
Hysteresis of auxiliary sensor
SVH
Maximum temperature
SVL
Minimum temperature
ADJ
Correction of measurement
FRE
Frost protection function
PON
Start up memory
FAC
Factory settings
INDICATION
2
L
NTC
5
4
6
. You can now change the following functions:
ELECTRICAL CONNECTION EXAMPLE WB 01 D
Possible settings
0: No additional NTC sensor
(internal sensor)
1: External floor temperature sensor
2: Internal sensor and external floor tempera-
ture sensor
5÷99°C
1÷9°C
5÷99°C
5÷99°C
-5÷+5°C
00: Off | 01: Activated
00: Off | 01: Activated
08: Do nothing | 00: Restore factory settings
Default
setting
0
42°C
2°C
35°C
5°C
+0.5°C
00
00
08