Herunterladen Inhalt Inhalt Diese Seite drucken

Knick VariTrans P 15000 Bedienungsanleitung Seite 22

Normsignaltrenner
Vorschau ausblenden Andere Handbücher für VariTrans P 15000:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Test voltage
Working
3)
voltage
(basic insulation)
Protection
against electrical
shock
4)
EMV
Surge withstand
Ambient
temperature
Power supply
Construction
22
4 kV~ input against output
against power supply
1000 V for overvoltage category II and pollution degree 2 to EN
61010-1
For applications with high working voltages, take measures to
prevent accidental contact and make sure that there is sufficient
distance to adjacent devices or sufficient insulation between them.
Reinforced insulation to EN 61010-1 and protective separation to
VDE 0100 Part 410 as defined in VDE 0106 Part 101 up to 300
V between input and output and power supply for overvoltage
category II and pollution degree 2. For applications with high
working voltages, take measures to prevent accidental contact and
make sure that there is sufficient distance to adjacent devices or
sufficient insulation between them.
EMC 89/336/EEC
DIN EN 61326
DIN EN 61326/A1
5 kV, 1.2/50 µs, to IEC 255-4
Operation
Transport and storage
22 to 230 V AC/DC ±10 %, approx. 1 W
AC 48 to 62 Hz
Modular case,
For dimensions see dimension drawings
Type H1 with pluggable screw clamp terminals
Type F1 with fixed screw clamp terminals
-10 to +70 °C
-40 to +85 °C

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis