Herunterladen Diese Seite drucken

Axis Communications A1610-B Installationsanleitung Seite 7

Vorschau ausblenden Andere Handbücher für A1610-B:

Werbung

-
Network Connector – Standard Ethernet wiring. Evaluated by UL when
powered from AXIS T8133 Midspan 30 W 1-port in PoE Mode B (alternative A).
-
Battery input is for connection to a listed UPS and has not been evaluated
by UL to UL 294.
-
Supervised inputs were not evaluated by UL for burglar use.
System considerations
-
Monitoring software was not evaluated by UL, and is for supplemental use.
Maintenance instructions
-
For maintenance instructions and for information about how to configure the
Axis product, see the User Manual.
Further information
-
Card formats verified by UL: ISO Cards Mifare 1K, 32 bits.
Power
-
Power in: 10.5–28 V DC, max 36 W, max 2.4 A at 10.5 V, max 0.9 A at
28 V. Power over Ethernet (PoE) IEEE 802.3at Type 2 Class 4, max 340 mA.
12 V battery as backup.
-
Relay: 2x relay NO/NC, max 2 A DC
-
Power out lock: 2x 12/24 V DC,
With PoE+: at 12 V, 11 W, at 24 V, 10 W
With DC in: at 12 V, 22.5 W, at 24 V, 18 W
-
Power out reader: 12 V DC, max 6 W
-
Auxiliary DC output: 1x 12 V DC output, max 200 mA
-
Total power budget for peripheral devices (locks, readers etc.): 2100 mA at
12 V if powered by DC, 1300 mA at 12 V if powered by PoE Class 4
I/O interface – I/O functionality
-
Reader I/O: DC output: 2x 12 V DC output, max 486 mA; 2x2 configurable
supervised inputs/outputs (digital input: 0 to max 30 V DC; digital output: 0
to max 30 V DC, open drain max 100 mA)
-
Reader data: OSDP/RS485 half duplex, Wiegand
-
Auxiliary: DC output: 1x 12 V DC output, max 200 mA, 4x configurable
inputs/outputs (digital input: 0 to max 30 V DC; digital output: 0 to max
30 V DC, open drain max 100 mA)
-
Door connections: 2x2 supervised inputs for door monitors and REX (digital
input: 0 to max 30 V DC)
-
External: 2x configurable inputs/outputs for auxiliary equipment (digital input:
0 to max 30 V DC; digital output: 0 to max 30 V DC, open drain max 100 mA)
Cable requirements
-
Wire size for connectors: CSA: AWG 28–16, CUL/UL: AWG 30–14
-
DC power and relay: AWG 18-16
-
Ethernet and PoE: STP CAT 5e or higher
AXIS A1610-B Network Door Controller
7

Werbung

loading