Herunterladen Inhalt Inhalt Diese Seite drucken

AFRISO Europress Betriebsanleitung Seite 75

Vorschau ausblenden Andere Handbücher für Europress:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
5
Mounting
In the case of underground tanks, the hydrostatic pressure of the ground
water acting on the tank bottom must not exceed 435 mbar.
The hydrostatic pressure of the stored liquid including any overlay pressure
must not exceed 435 mbar.
5.1
Preparing mounting
 Verify that the audible alarm signal of the control unit can always be
heard, even in the case of ambient noise.
If audibility cannot be ensured, you must install an additional alarm unit at a
suitable location in the building (for example, additional alarm unit ZAG 01,
horn KH 1 or combined alarm light and horn from AFRISO).
5.2
Mounting the product
 Verify that the product is mounted to an even, rigid and dry wall at eye
level.
 Verify that the product is accessible and easy to oversee at all times.
 Verify compliance with the permissible ambient conditions at the product.
 Verify that the product is protected against water and splash water.
 Verify that the product is protected from direct atmospheric influences if it
is installed outdoors.
- Use an AFRISO protective housing.
Mounting
Europress
EN
17

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis