Herunterladen Inhalt Inhalt Diese Seite drucken

Pipe Connection; Water Piping Work - Mitsubishi Electric PXZ-5F85VG Installationsanleitung

Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 19
3-3. PIPE CONNECTION
• The connected pipe size differs depending the models and the capacities of indoor units.
Indoor unit capacity
15 ~ 25 35 ~ 42
Liquid pipe size
ø6.35
Indoor unit:
M series
Gas pipe size
ø9.52
Liquid pipe size
ø6.35
Indoor unit:
S series
Gas pipe size
ø9.52
Liquid pipe size
-
Indoor unit:
P series
Gas pipe size
-
*1 Use a joint pipe if the connection of the indoor unit differs.
• Use tightening torque table above as a guideline for indoor unit side union
joint section, and tighten using two wrenches. Excessive tightening dam-
ages the flare section.
1) Do not apply refrigeration oil on screw threads. Excessive tightening torque
will result in damage on the screw.
2) For connection, first align the center, then tighten the first 3 to 4 turns of
flare nut by hand.
3) Tighten the flare nut with a torque wrench as specified in the table.
• Over-tightening may cause damage to the flare nut, resulting in refrigerant
leakage.
• Be sure to wrap insulation around the piping. Direct contact with the bare
piping may result in burns or frostbite.
4) If the length of the connection pipe is 10 m or less when connecting to a
floor-standing ATA indoor unit, it is recommended to install the optional
muffler (sold separately).
For the installation method, refer to the construction manual for the muffler.
(Optional muffler model name: MAC-001MF-E)
Type
Model
Floor standing
MFZ-KT**VG
3-4. WATER PIPING WORK
3-4-1. Minimum water quantity
Refer to the indoor unit installation manual.
3-4-2. Available range
(Water flow rate, return water temp.)
Ensure the following water flow rate and return temperature range in the water circuit.
These curves are related to the water quantity.
26.0
24.0
22.0
20.0
18.0
16.0
14.0
12.0
10.0
5.0
3-5. INSULATION AND TAPING
1) Cover piping joints with pipe cover.
2) For outdoor unit side, surely insulate every piping including valves.
3) Using piping tape (E), apply taping starting from the entry of outdoor unit.
• Stop the end of piping tape (E) with tape (with adhesive agent attached).
• When piping have to be arranged through above ceiling, closet or where the
temperature and humidity are high, wind additional commercially sold insula-
tion to prevent condensation.
50
60
71
ø6.35
ø6.35
ø6.35
ø6.35
ø9.52
ø9.52 *1
ø12.7
ø12.7
ø6.35
ø6.35
ø6.35
ø9.52
ø9.52
ø12.7
ø15.88
ø15.88
ø6.35
ø6.35
ø9.52
ø9.52
ø12.7
ø12.7
ø15.88
ø15.88
Optional Muffler
MAC-001MF-E
CAUTION
When there are the ports which are
not used, make sure their nuts are
tightened securely.
Unavailable range
10.0
15.0
Water flow rate [L/min]
Indoor unit: ecodan Cylinder unit / Hydrobox
Indoor unit: DHW tank
WARNING
When installing the unit, securely
connect the refrigerant pipes before
starting the compressor.
Indoor unit connection
Flare nut
Internal thread side
Tighten the flare nut
with a torque wrench.
Outdoor unit connection
Tighten the flare nut
with a torque wrench.
Available range
(10L~15L)
(15L~25L)
(25L~60L)
(over 60L)
Note:
Be sure to avoid the unavailable range during defrosting.
Otherwise, the outdoor unit is insufficiently defrosted
and/or the heat exchanger of the indoor unit may freeze.
20.0
25.0
Liquid pipe size
ø6.35
Gas pipe size
ø12.7
Liquid pipe size
ø6.35
Gas pipe size
ø9.52
Union joint
External thread side
Grip the nut on the
union joint with a spanner.
en
11

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis