9 Unit installation
INFORMATION
All piping lengths in the tables below are maximum
equivalent piping lengths.
L1
C
53
3
L1
L1
C
C
13
93
1
4
Explanation of the flue systems
Category in accordance with CE
C
Horizontal flue system. Discharge in the outside wall. Inlet
13
opening for the air supply is in the same pressure zone as the
discharge.
C
Vertical flue system. Flue gas discharge via the roof. Inlet
33
opening for the air supply is in the same pressure zone as the
discharge.
C
Joint air supply and flue gas discharge duct (CLV system).
43
Twin pipe or concentric.
C
Separate air supply and separate flue gas discharge duct.
53
Discharge into different pressure zones.
C
Free in the market available flue material with CE approval.
63
C
Joint air supply and flue gas discharge duct (CLV system).
83
Discharging into different pressure zones.
C
Air supply and flue gas discharge duct in shaft or ducted:
93
concentric. Air supply from existing duct. Flue gas discharge
via the roof. Air supply and flue gas discharge are in the same
pressure zone.
The horizontal flue MUST be installed under a 3° fall towards the
boiler (50 mm per metre) and MUST be supported with a minimum
of 1 bracket at each meter length. Best recommended position of the
bracket is just before the joint.
INFORMATION
Flexible flue gas lines may NOT be used in horizontal
connection sections.
C
(1)
C
(2)
13
33
60/100
60/100
L1 (m)
L1 (m)
10
10
C
(1)
C
(2)
C
13
33
80/125
80/125
80/125
L1 (m)
L1 (m)
L1 (m)
29
29
10
Installation and operation manual
20
C
33
2
C
(1)
C
(2)
13
33
Twin-80
Twin-80
L1 (m)
L1 (m)
80
21
(4)
C
(3)
93
53
80
60/100
60
L2 (m)
L1 (m)
L2 (m)
25
6
1
1
10
INFORMATION
The above installation examples are just examples and
can differ on some details.
For example: a wall terminal through the façade.
For example: a vertical roof terminal.
Do NOT mix flue materials from different suppliers.
Only as twin pipe system.
Concentric flue system between the gas boiler and the duct.
Special remark regarding C
: The maximum lengths for L1 and L2
53
are related to each other. First determine the length of L1; then
make use of the graph below to determine the maximum length of
L2. For example: if the length of L1 is 2 m, L2 can maximally be 8 m
long.
Daikin Altherma hybrid heat pump – gas boiler module
EHYKOMB33AA
4P353067-1L – 2022.09