WIRING DIAGRAMS
Unit table/Diagrams
.....
Electrical connections to be made by installer
BU
Blue (Med. speed)
BK
Black (Max. speed)
Brown
BN
CI12
Digital input common
CN
Terminal board
DI1
Remote Heat/Cool Digital Input
DI2
Remote On/Off Digital Input
External auxiliary contact
EXT
F
Fuse (not supplied)
GN
Green
GY
Grey
Circuit breaker (not supplied)
IL
IPM
Circuit board for UTN units
KP
Circuit board to control 4 indoor units
L
Phase
Fan motor
M
MS
Flap microswitch
N
Neutral
PE
Ground
RHC
Heating/Cooling remote selecting switch
Heating element
RE
RD
Red (Min. speed)
SA
Air sensor
SC
Wiring box
Water sensor
SW
TSA
Automatic safety thermostat
TSM
Safety fuse
Vo
-
V1
Min. speed
Med. speed
V2
V3
Max. speed
VC
Solenoid valve - Cooling
VH
Solenoid valve - Heating
Solenoid valve –Cool/Heat.
VHC
WH
White (common)
YE
Yellow
KR
Heating element relay
Installation and operation manual
10
INSTALLATION OF WALL-MOUNTED
CONTROLLER
For wall mounting of the controller it is advisable to use an
electric box behind the controller to accommodate the cables.
NB: Prior to installation, carefully remove the protective film
from the display; removal of the film may cause some dark
streaks to appear on the display but these will disappear
after a few seconds and are not signs of a controller defect.
Instructions for installation:
 R emove the fastening screw of the controller (see figure 4).
 I f a 503 electrical enclosure is used, pass the cables
through the slot at the bottom of the controller and use the
holes provided for fastening. (see figure 5).
 O therwise, in the wall where you wish to mount the control-
ler, drill holes to match up with the fastening slots (5x8mm)
on the base of the controller; pass the cables through the
slot on the base and screw it to the wall (previously drilled).
(see figure 6).
 M ake the electrical connections to the indoor unit termi-
nal block as per the wiring diagram.
 C lose the controller with the screw provided.

TECHNICAL DATA

90-250Vac 50/60Hz
Power supply
Electrical input 8W
Protection fuse 500mA delayed
Operating temp.
Range 0-50°C
Storage temp.
Range -10-60°C
NO 5A @ 240V (Resistive)
insulation: coil-contact distance 8 mm
Relay
4000V coil-relay dielectric
Max ambient temperature 105°C
Connectors
250V 10A
Clean contact
Digital inputs
Closing current 2mA
Max. closing resistance 50 Ohm
Analog inputs
Temperature sensors
Power outputs
Relay (see above)
NTC sensors 10K Ohm @25°C
Temperature sensors
Range -25-100°C
FWEC1
Standard electronic controller
FC66002763