The PTS 230-10 has an internal glass fuse of 8Amp. at the exit. If it
needs replacing, always use a fuse of the same value.
With model PTS 230-25 it is advisable to place an external fuse on the
output. Use a slow fuse of max. 25 Amp.
Important
Make sure that the system has been completely isolated at all times
when replacing a fuse!
Switching PurePower(Plus) inverter on/off (X-com)
The PTS 230-25 has an X-com connection. This plug & play connection
is specially for the PurePower(Plus) inverters by Xenteq (from 600Watt)
and provides the option of switching the inverter off or on automatically.
On the moment that the mains voltage is detected, the PTS switch box
will switch off the inverter. If the mains voltage is lost, the inverter will be
switched on again automatically. In this way the inverter is not switched
on unnecessarily when the mains voltage is available.
A t-splitter is available for use of the X-com function in combination with a
PPR remote for manual control
With the PTS 230-25 is a connection cable of 1 meter supplied,
specifically intended for connecting the PurePower(Plus) inverter.
You will find a grommet on the left side of the PTS housing. Cut away the
part that is needed for guiding the cable.
Connect the cable to the RJ45 connector inside the PTS switch box.
Connect the other side of the cable to the 'remote' connector of the
inverter.
Note: set the on/off switch of the inverter to the OFF position,
otherwise this function will not work.
When switching on, the inverter will always do a short self-test first.
Therefore the 230VAC output will be present after 3 to 4 seconds.
If no mains voltage is present and the inverter will not be used for a long
time, it is recommended to switch off the inverter manually (disconnect
x-com connection or via the remote control).