H = distance required for correct
installation of adapters
26
5.2 Mounting kit with window
for DV DIASTAR DN 15 –DN 150
5.2.1 Place the o-ring (1) in the slot provided
in the mounting kit (2).
5.2.2 Screw the mounting kit onto the DV-
DIASTAR (Check the distance H,
see below).
5.2.3 Mount the needle (3) on DV DIASTAR
(3x)
(For DN 100–150 place the needle
protector on the needle and then insert
in adapter).
5.2.4 Mount the DSR positioner (4) on the
adapter of the mounting kit (2) and
fasten with threaded studs (5).
Attention: Make sure that the
connector A is vertically in line with the
connections on the DV DIASTAR.
5.2.5 Remove the lower protective plug (FC)
(6). Connect rapid connector (7) on
actuator and positioner.
5.2.6 Connect hose (8) between DV DIASTAR
and DSR positioner (connector A).
5.2.7 Connect air supply to connector P.
Window version
Diastar &
Positioner
DN 15 Gr. 2
DN 20 Gr. 2
DN 25 Gr. 2
DN 25 Gr. 3
DN 32 Gr. 3
DN 32 Gr. 4
DN 40 Gr. 4
DN 40 Gr. 5
DN 50 Gr. 4
DN 50 Gr. 5
DN 65
DN 80
DN 100
DN 150
All dimensions in mm
Mechanical check
Area H
closed
50.7–52.7
55.4–56.3
54.2–57.6
54.7–56.8
56.3–57.7
48.7–58.3
51.9–54.5
51.7–54.0
56.1–57.9
53.3–56.8
70.2–73.4
75.3–76.9
74.6–87.4
76.5–87.4