S7-FCT also allows you to configure selected F-I/Os from Siemens that are not contained in the hardware catalog of supported
Siemens configuration software.
Configuration software
STEP 7 (TIA Portal) V17
STEP 7 (TIA Portal) V16
STEP 7 (TIA Portal) V15.1
STEP 7 (Classic) V5.7
STEP 7 (Classic) V5.6 SP2
STEP 7 (Classic) V5.6 SP1
STEP 7 (Classic) V5.6
STEP 7 (Classic) V5.5 SP4
Software of other manufacturer
Configuring the ET 200eco PN F-DI 8 x 24 VDC, 4xM12 / F-DQ 3 x 24
VDC/2.0A PM, 3xM12 (6ES7146-6FF00-0AB0) as of firmware
version V1.0.0 or later
In TIA Portal, the "IO Tags" tab displays more tags than are supported by the F-module.
Configuring F-I/O module parameters using GSDML
You specify the properties of the F-I/O module in STEP 7 using various parameters. Depending on the settings, not all
parameters are available.
You set the parameters of the module as follows:
1. Insert the IM 157-1 PN interface module. When using STEP 7, the interface module is found in the hardware catalog under
"Other field devices->PROFINET IO->I/O->SIEMENS AG->ET 200AL".
2. Insert the F-I/O module. When using STEP 7, the F-I/O module is found in the hardware catalog under "Module->DIQ->F-DI
4+F-DQ 2x24VDC/2A, 4xM12". Select PROFIsafe V2.4 or PROFIsafe V2.6 based upon the specifications of your fail-safe
controller. If you are using Siemens fail-safe controllers, select PROFIsafe V2.4 if you are using an S7-300 or S7-400 F-CPU or
select PROFIsafe V2.6 if you are using an S7-1200 or S7-1500 F-CPU.
3. Access the F-I/O module's parameters in your programming package. To display the module's parameters in STEP 7, on the
Device view or Device overview select the F-I/O module and select the module's "Properties" tab.
4. In the "Properties" view, on the "General" tab, select "PROFIsafe" and the drop-down arrows for "Module parameters>I/O
parameters" to see a subset of the properties of the "PROFIsafe" and "I/O parameters".
5. Set values for "PROFIsafe" or "I/O parameters" in the right side property fields.
6. Right click the F-I/O module name in the Device view and click "Start device tool ..." to launch S7-FCT.
Select "F_iPar_CRC calculation" and click Start.
If asked, choose and confirm the desired communication interface.
Examine the parameters, and if correct, press "Confirm i-parameters" to calculate the F_iPar_CRC.
If parameters are not correct, close out of S7-FCT and return to the module Properties dialog to correct the parameter
settings.
Click the copy button next to the hexadecimal representation of the F_iPar_CRC (left value) to place this value on the
clipboard.
Close out of S7-FCT.
7. In the "Properties" view on the "General" tab for the module, select "PROFIsafe" in the tree and paste the clipboard value into
the F_iPar_CRC field.
8. A successful compile and download of your hardware configuration to an F-CPU automatically configures your F-I/O module.
Assigning PROFIsafe addresses for F-I/Os
These are the three basic steps for assigning PROFIsafe addresses:
2
Support as of
or later
Upd1 or later
Upd5 or later
or later
HF2 or later
HF5 or later
HF5 or later
HF19 or later
Information on installation
STEP 7 online help
STEP 7 help
Documentation of the manufacturer
Configuring ET 200eco PN Fail-Safe Modules with a GSDML File
Requirements
S7-FCT V2.0 or
later
A5E46726754-AC, V1.1, 02/2022