Function Description - Weidmuller PV Next-Serie Bedienungsanleitung

Feuerwehrschalter
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Product description
L
-XD10
N
PE
O1
-XD11
O2
Figure 3.4 Block diagram

3.2 Function description

Inside the box, the PV string cables are fed from the input
to the output terminal via a motorised DC switch discon-
nector. Up to two PV string cables are combined on one
output.
The integrated electronics with energy storage enable the
"Fireman switch" function: if the 100 - 230 V AC supply volt-
age is interrupted for more than 5 seconds, the integrated
motor automatically turns the switch to the off position. This
safely disconnects the connection between the PV mod-
ules and the inverter. The 100 - 230 V AC supply can be
interrupted using an additional switch, by deactivating the
fuses in the sub-distribution or by shutting down the build-
ing connection.
Once the 100 - 230 V AC supply voltage is restored for
more than 5 seconds, the integrated motor automatically
moves the switch to the on position.
The motorised DC switch-disconnector also switches to the
off position in the following situations:
– The temperature in the enclosure exceeds 100 °C
– Defect in the electronics
30
1
AC
2
3
DC
1
2
LED1 LED2
24 V DC
DC
0 V DC
C
DC
to S1 (Turn DFS ON)
to S1 (Turn DFS OFF)
µC
to LED1 (AC power present)
to LED2 (UPS power OK)
DC
AC
Figure 3.5 Connection example
1
S1
2
-XD12
S2
3