Switch S5; Switch S6 - AMPERFIED Wallbox Energy Control Bedienungsanleitung

Lastmanagement
Vorschau ausblenden Andere Handbücher für Wallbox Energy Control:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
English
External load management: configuration of
bus IDs of follower Wallboxes 1 to 15
Set the bus IDs of follower Wallboxes 1-15 using
switch S4.
Please note:
Never assign double bus IDs.
Never use the bus ID '0'.
Bus-ID
S4/1
S4/2
0
OFF
OFF
1
OFF
OFF
2
OFF
OFF
3
OFF
OFF
4
OFF
ON
5
OFF
ON
6
OFF
ON
7
OFF
ON
8
ON
OFF
9
ON
OFF
10
ON
OFF
11
ON
OFF
12
OFF
ON
13
ON
ON
14
ON
ON
15
ON
ON
4.4
Switch S5
Switches S5/1, S5/2 and S5/3 are not needed on
any of the follower Wallboxes. Set these switches
to OFF.
Switch S5/2 is not required on the leader Wallbox.
Set the switch to OFF.
Configuration as leader and follower via switch S5/4
S5/4
ON
Leader
OFF
Follower
Configuration of blocking function (in leader
Wallbox) via switch S5/3
The Wallbox has an input via which it can be
blocked by an external switching element
(key-operated switch or similar device; see
assembly instructions).
Use switch S5/3 to specify whether this blocking is
to affect only the leader Wallbox or all Wallboxes.
22
S5/3
OFF
ON
4.5
The first and last devices on the RS485 bus must be
S4/3
S4/4
connected with a terminating resistor.
OFF
OFF
Terminating resistor for last Wallbox
OFF
ON
Use micro switch S6/2 to connect the built-in termi-
ON
OFF
nating resistor on the last follower Wallbox. Switches
ON
ON
S6/1, S6/3 and S6/4 are not used. Set these switches
OFF
OFF
to OFF position.
OFF
ON
S6/2
ON
OFF
OFF
ON
ON
ON
OFF
OFF
OFF
ON
Local load management
ON
OFF
Leader
ON
ON
OFF
OFF
OFF
ON
ON
OFF
S6/2
ON
ON
Terminating resistor for leader Wallbox
Use micro switch S6/2 to connect the built-in termi-
nating resistor on the leader Wallbox. Switches S6/1,
S6/3 and S6/4 are not used. Set these switches to
OFF position.
External load management
Leader Follower1 Follower2
HEMS terminating resistor
When using an external control unit, terminate
the bus line with a 120 Ohm resistor. Observe the
specifications from the manufacturer of the external
control system here.
Only the leader Wallbox
is blocked.
All Wallboxes are
blocked.
Switch S6
Bus termination inactive
Bus termination active
Follower1 Follower2
Follower3 Follower4
RS485
Follower3 Follower4 Follower5
RS485
120 Ohm
S6/2
S6/2