Dip Switch Configuration - Window Master WCC 106 BT Installationsanleitung

Motorcontroller
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

DS
DIP switch block with 8 DIP switches.
1
Maintained action
2
Rain delay
3
Extended hand timer
4
Surveillance
5
MotorLink®
6
100% speed
7
Accumulated step
8
Motor line 2, motors run independently
Factory setting = OFF
See chapter "DIP switch configuration" for detail information.
↓ ↑
Close / Open all windows
K1
Reset
K2
FW update; to be used in line with firmware updates
K5
Bluetooth pairing, used when the MotorController is to be paired with a remote control
Yellow LED that indicates error on the MotorController. As a reference to fault output X9.
LED 1
If the diode is off, there is no error/failure. Output X9 is OFF.
See chapter, "Status and troubleshooting via LED on the MotorController" for more information.
Green LED that shows status of MotorController.
If diode lights constantly, there is no error/failure.
LED 2
If the diode blinks, see chapter, "Status and troubleshooting via LED on the MotorController" for more
information.
Green LED that shows status of the motor line 2.
LED 3
The diode can light constantly or blink asynchronously.
See chapter, "Status and troubleshooting via LED on the MotorController" for more information.
Green LED that shows status of the motor line 1.
LED 4
The diode can light constantly or blink asynchronously.
See chapter, "Status and troubleshooting via LED on the MotorController" for more information.

DIP switch configuration

10
The MotorController has 8 DIP switches for easy configuration. The factory setting for the DIP switches is OFF.
DIP
Description on the
switch
MotorControlleren
1
Maintained action
2
Rain delay
3
Extended hand
timer
4
Surveillance
®
5
MotorLink
6
100% speed
7
Accumulated step
ON: the actuators open/close completely when the comfort keypad is pressed.
OFF: the actuators run for as long as the comfort keypad is being pressed.
ON: the rain signal must be active min. 60 sec. before the actuators begin to close.
OFF: the actuators begin to close as soon as the rain signal is activated.
ON: after manuel override the actuators are locked for 2 hours (except rain/safety signals).
OFF: after manuel override the actuators are locked for 30min (except rain/safety signals).
ON: activate cable surveillance on input X10.1 (rain). The Input must be terminated with 10k
resistor.
OFF: no cable surveillance.
ON: MotorLink® motors are connected to the MotorController.
It might be necessary to reset the MotorController when activating this DIP switch.
OFF: ±24V standard motors are connected to the MotorController.
ON: actuators run with 100% speed, when run manually.
(this setting requires MotorLink® actuators and that DIP switch 5 is set to "ON")
OFF: actuators run with 75% speed, when run manually.
ON: actuators open/close in steps, when a thermostat e.g., WLA 110 is connected to the
MotorController and the setpoint is exceeded.
Opening step: 5% for every 5min
Closing step: 10% for every 10min
OFF: actuators open/close completely when a thermostat e.g., WLA 110 is connected to the
MotorController and the setpoint is exceeded
DIP switch position