CENTRAL CONTROL SC-SL4-AE, SC-SL4-BE
INSTALLATION MANUAL
Please read this manual thoroughly and follow it carefully when carrying out installation work.
Please also refer to the installation manuals for the indoor and outdoor units.
The appliance must be installed in accordance with national wiring regulations.
The product is a precision equipment, so please handle it with enough care to prevent the unit damage due to falling
and being stepped on.
Before touching the terminal block, turn off the power supply.

Safety Precautions

Before starting installation work, read the "Safety Precautions" thoroughly in order to ensure you carry out installation
correctly.
Safety Precautions are divided into "Warning
WARNING : Indicates a high possibility that serious injuries or death may occur if the unit is not installed correctly.
CAUTION : Indicates a possibility that serious consequences may occur depending on circumstances.
Please be sure to follow the instruction.
After completing the installation, carry out a test run to confirm that no abnormalities occur, and show customers how to
use the unit according to the User's Manual. Please ask customers to keep the Installation Manual on hand.
Please ask your dealer or relevant professionals to install the unit. Installing the unit by yourself may result in defects,
which may lead to electric shocks or fire.
Install the unit correctly according to the Installation Manual. If any of the installation steps are not followed, electric
shocks or fire may occur.
Be sure to only use the included accessories and specified parts when installing the unit. Otherwise, it may result in
electric shocks or fires.
The electrical work should be performed by qualified electrical engineer, according to <Electrical Standards>, <Local
electrical safety regulations> and wiring specification. If any of the installation steps are not followed, electric shocks
or fire may occur.
When wiring, ensure solid connection and fasten specified cables securely so that terminal connections may not be
subject to external force working on cables. Incomplete connection for terminal wiring may cause electric shock and
resultant fire.
Please perform grounding work.
Please do not connect the ground wire with gas pipes, water pipes, lightning rod and telephone ground wire.
Incomplete grounding work may cause electric shock.
Please do not install the central control at the following places.
1.
Oil fog filled place, oil spraying and steamy location such as kitchen, etc.
2.
The place where corrosive gas such as sulfur dioxide generates.
3.
The location with machine that generates radio wave.
It may cause abnormality in the control system and abnormal running.
4.
The location at risk of flammable gas leaking.
The place where volatile combustible substance such as paint thinner and gasoline exists.
By any chance the gas leaks and it accumulates around the equipment, it may cause ignition.
1
Applicable Models
All models for Super Link
2
Accessories
Please check the following accessories.
Central control
1 unit
4 pieces for installing on the
control box (10mm)
Pan-head screws (M4)
4 pieces for embedding in a
wall (40mm)
4 pieces (8mm) for installing
Pan-head screws (M3)
the central control
For SC-SL4-BE
CD-ROM (Energy consumption calculation software)
Installation procedure
(1) Remove the upper case
Take out two screws using a
1
3
cross slot screwdriver. (Do not
lose the screws)
Pull the upper case a little
2
2
forward and push above. Then,
upper case can be removed.
Caution
Please do not install
facing upward or at
a slant.
Allowed
Not allowed Not allowed
Embed signal wire and power supply wire in the
wall beforehand.
Connect wires to the terminal block.
Confirm power supply voltage and connect
correctly.
4

Electric Wiring

For safety reasons, please use the round crimping terminals with insulated sleeves for connecting all wires to the central control.
Please do the grounding work. Please do not connect earth line with gas pipes, water pipes, lightning rods and grounding line of
telephone.
Please do not turn on the power supply (local switch) until all of the work is completed.
Please wait at least two minutes after the indoor and outdoor units are turned on before turning on the power supply.
Except for the central control in the figure, all of the components are obtained at the site (wires, switches, relays, power supply, lamps,
etc.)
Please be sure to build the circuit breaker which is easily accessible with building equipment's wiring.
Pease be sure to use the supplied round crimped terminals when connecting wires to the power supply terminal block and Super Link
terminal block.
Before connecting the wires, remove the cover of the terminal block. After the work is completed, fix the cover of the terminal block as
before. The cover is used to prevent electric shock due to accidental contact.
Please use a gas meter or watt-hour meter, demand input device and emergency stop input device which comply with a relevant IEC
Safety Standard.
Wiring Outline
Power supply
AC100-240V
50/60Hz
L1, L2
Local switch
Grounding work
The calculating data taken out by way of USB memory
(accessory of SC-SL4-BE)
LAN
Emergency stop signal input
Demand signal input (2 points)
Wiring Specifications
Power supply wire
Local switch
Super Link signal wire
(Note 1, Note 2)
The wire for operation output, error output,
emergency stop and demand input
The wire for gas meter or watt-hour meter
Grounding wire
Note 1: When this central control is used, use a shielded wire for the Super Link signal wire. Ground both ends of the shielded wire.
(Please wire the ground of the central control at
Note 2: If the indoor and outdoor units connected to the network are all compatible units with New Super Link, a total wire length of 1500m per line is
possible (maximum distance: 1000m). However, be sure to use a 0.75mm
information, please contact your sales representative or dealer.
" and "Caution
".
WARNING
CAUTION
User's manual (CD-ROM)
Installation Manual
(this document)
Installation bracket (front)
Installation bracket (rear)
Round crimping terminal
1 unit
USB Memory
(2)
Installation outline
Be sure to use the attached installation
brackets.
Wall
Central
M3 pan head screw × 4 positions
control
1
Installation
bracket
Installation
(rear)
bracket (front)
Fasten the central control to the front side of the control box or a hole
in the wall using the M3 screws.
Wire separately the power supply wire and the signal wire for
preventing malfunctions.
Grounding
work
3 Super Link systems
Power
supply
Operation output
Power
supply
Malfunction output
Power pulse input from gas meter or watt-hour meter
(8 points) (in case of SC-SL4-BE)
1.25mm
2
10A
Shielded wire (double-core, 0.75mm
- 1.25mm
).
2
2
Max. 1000m per line (Max. distance: 1000m, Total wire length: 1000m)
Shielded wire (double-core, 0.75mm
- 1.25mm
).
2
2
Maximum length: 200m per system
Shielded wire (double-core, 0.75mm
- 1.25mm
).
2
2
Maximum length: 200m per system
0.75mm
- 6mm
2
2
Ground position "b" of "System Wiring" in the diagram)
2
wire diameter if the total wire length exceeds 1000m. For further
3

Installation Work

Please install the central control after turning off the power for fear of electric shock.
Please arrange or protect the wiring so that excessive force is not applied to the electrical wires.
Installation Place
Please install in an indoor location that is not exposed to electromagnetic waves, water, dust, or other foreign substances.
PJZ012D091
The operating temperature range of this product is from 0°C to 40°C.
Install in a location where the ambient temperature remains within the operating temperature range.
However, if the operating temperature range is exceeded, be sure to implement corrective measures such as installation of a cooling fan.
Be aware that continued usage of this central control outside the operating temperature range can result in operation problems.
Space Required for Installation
<Opening Space for the Installation>
Create a hole in the wall as shown in the figure above.
Be sure to check the dimensions required to correctly install
the unit.
(1)
In case of installing on the control box
Please use the control box of the size of 300mm
or larger.
Please be sure to lock the control box to protect persons from electric
shock. Avoid usage of heat-retaining materials and heat-insulating
materials because these can result in heat buildup and adversely
affect the operation of the central control.
Caution
Please do not install devices that can cause the ambient
temperature to rise in the same control box. Also, do not install
multiple controllers in the same control box. These can cause
heat to build up and result in false operation. If multiple central
control must be installed in the same control box, take corrective
measures to ensure that the temperature in the control box does
not rise above 40°C such as by installing cooling fans.
<Service space>
Front of the central control
500mm or larger
Bottom of the central control
100mm or larger
(2)
In case of embedding in a wall
Be sure to use the attached installation brackets. Alternatively, you
can use SLA3R-BX for SC-SL3N. Please be sure to use for protecting
persons from the electric shock. Please check that the sufficient space is
available in the wall. When the inside of the wall is divided and have a
cavity, please create space more than 0.08m
If there is partition on the left, right, top and bottom of the central
1 unit
control, please create a space that is 105mm or deeper.
1 unit
Example1
1 piece
Example2
1 piece
Example3
Large size × 2 pieces,
Minimum
Small size × 6 pieces
1 unit
System Wiring
Upper
case
(1)
The upper tier of Terminal Block (*)
LCD
L1
Power supply
AC100-240V
50/60Hz
(*1)
(*2)
(2)
The lower tier of Terminal Block
FGND
Caution
Do not connect power supply wire to another terminal block.
When you connect by mistake, damage and damage by fire of the
electric part are caused, and it is very dangerous.
Please check the wiring thoroughly again before turning on power.
The demand signal input is configured for two points. To configure the
3 level setting, contact your sales representative or dealer.
Notice
Please choose the new or previous setting of Super Link (SL) in the display of the main unit. (See user's manual)
It is necessary to change if the connection network is for previous Super Link. Whether the real connection network is new Super Link or previous Super Link
depends on the type of connected indoor unit,outdoor unit,etc. Inquire the agents or dealers for more information.
When choosing the new Super Link Communication setting, 1 system wiring can connect up to a maximum of 128 units. Be sure to connect wiring to the Super
Link system 1. Be careful not to connect to the Super Link system 2 or 3, as the main unit will not be recognized.
Power switch
The power switch is lower front of the central control. After installation is completed, turn the power switch ON.
Note that the central control does not start up unless the power switch is turned ON.
(It is turned ON by factory default.)
Note
Please peel off the protection sheet of the screen when you pass the central control to the customers.
Before you mount the upper case, please peel off the sheet.
After checking the wiring and doing power switch operation, when the screen is not displayed, please contact
the shop where the central control was purchased. This product consists of the exclusive parts, and you can not
exchange the electrical equipment. Please do not disassemble other than what is stated in this instruction manual.
Other Information
This central control is electronic and independently mounted control.
The type of this central control is automatic action for which the manufacturing deviation and the drift of its operating value, operating time or operating
sequence have not been declared and tested under the standard.
The actions of this central control are full-disconnection on operation, a trip-free mechanism which cannot even momentarily be reclosed against the fault, an
action which can only be reset by the use of a tool, and an action that does not require any external auxiliary energy source of electrical supply for its intended
operation.
The rated impulse voltage (impulse withstand voltage) is 2500V.
The surface of touch panel and front cover produce an increase of temperature of about 15 degrees.
The definitions of types of control are electrical control, automatic control, and operating control.
The lifetime of the keying of touch panel is ten million times. The lifetime of LCD is about 80,000 hours.
176
ø5 × 4
220
Insert the installation bracket (rear) into the rear of the
wall through the hole, and secure the bracket.
× 400mm × 120mm
500
100
. Refer to the table below.
3
a (height)
b (width)
c (depth)
space (m
)
3
(mm)
(mm)
(mm)
900
800
110
0.08
1800
400
110
0.08
1000
400
200
0.08
600 or larger
400 or larger
110 or larger
The back of the central control
L1 L2
Ground
position "a"
FG FG
L2
DO1 DO1- DO2 DO2- COM
DI1
COM
DI2
+
(*1)
+
(*1)
Power
Power
supply
supply
Please be
(*2)
(*3)
sure to use
the accessory
Operation
Malfunction
Emergency stop
Demand signal
terminals (L).
output(O1)
output(O2)
signal input (I1)
input (I2)
Power supply : DC 24V
Maximum rating current : 40mA
Factory default of error output (normal operation) is closed status. You can choose "Open"
status for malfunction output during normal operation. Please refer to the user's manual.
FGND
COM
PI1
COM
PI2
COM
PI3
COM
Power input from gas meter or watt-hour meter (8 points)
(in case of SC-SL4-BE)
In the wall
Pan-head
screw (M4)
Installation
bracket (rear)
Installation
Installation
bracket (front)
bracket (rear)
Internal wall
Fasten the installation bracket (front) and installation
bracket (rear) as shown in the figure above.
The top and bottom of the brackets can be easily
identified. Be sure to check the " UP" mark to install
it right side up.
<No partition>
<With partition>
Lead-in
cable
a
Central
control
b
Internal
wall
Inner wall
Beam of
105mm or
materials
building
larger
Installation Position
Install the central control so that the center of the screen will
be at the same height as the eye level of people who will
frequently use the unit.
The recommended position is that the center of the screen
becomes within +10, -30 degrees from eye level.
(30cm)
Central control
10°
5cm
30°
17cm
Ground position "b" for
Super Link system signal wire
Terminal block (two tiers)
LAN
Please be sure to use the accessory terminals (S).
(Same for A2, B2, A3, B3)
COM
DI3
A1
B1
A2
B2
A3
B3
(*3)
(*3)
Demand signal
Super Link system 2
input (I3)
(*4)
Super Link system 1
(*3)
No-voltage a-contact input Contact capacity : DC12V, 10mA
(*4)
When choosing the new Super Link setting, only system 1
functions effectively.
PI4
COM
PI5
COM
PI6
COM
PI7
COM
PI8
Please connect the gas meter or the watt-hour meter that satisfies the
specification below.
the meter with pulse transmitter
the meter with pulse width of 100ms or more
The energy consumption calculated by this central control does not conform to
OIML, and there are no guarantees concerning the results of the calculations.
Power switch
Partition
c
Super
Link
system 3

Werbung

Inhaltsverzeichnis
loading

Diese Anleitung auch für:

Sc-sl4-beZumh19

Inhaltsverzeichnis