Herunterladen Diese Seite drucken
Honeywell TC808 Serie Installations- Und Wartungsanleitung Für Das Fachhandwerk
Honeywell TC808 Serie Installations- Und Wartungsanleitung Für Das Fachhandwerk

Honeywell TC808 Serie Installations- Und Wartungsanleitung Für Das Fachhandwerk

Thermomelder der

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

102 mm
B501AP
INSTALLATION AND MAINTENANCE
ENGLISH
INSTRUCTIONS FOR THE TC808 SERIES
ADVANCED THERMAL FIRE SENSORS
GENERAL DESCRIPTION
The TC808 Series intelligent thermal sensors are plug-in type fire sensors that use a
single thermistor sensing circuit to provide early warning of developing fires, together
with addressable communication with the fire panel.
The TC808ES1028 / TC808EIS1028 provides fixed 58
temperature sensing (Class A1R).
The TC808ES1002 / TC808EIS1002 provides fixed 58
The TC808ES1051 / TC808EIS1051 provides fixed 78
(Class BS).
These sensors are designed for open area protection and must only be connected to
fire panels that use a compatible proprietary communication protocol for monitoring
and control.
Models with the letter 'I' contain an isolator, if installing this version check the panel
documentation for details of how many isolators can be used on a loop.
Two LEDs on each sensor light to provide a local 360
of LEDs are dependent on panel). Remote LED indicator capability is available as an
optional accessory wired to the standard base terminals (again dependent on panel).
SPECIFICATIONS
Operating Voltage Range:
Max. Standby Current (no comm.): 160 µA @24 V and 25
(comm. LED blink enabled - 5 sec) 300 µA @24 V and 25
(Read 16 sec. LED blink 8 sec)
Max. Alarm Current (LED on):
Operating Humidity Range:
Isolator Characteristics ('I' Versions Only)
Maximum rated continuous current with the isolator closed (Ic max): 1A
Maximum rated isolator current (under short circuit) (Is max): 1A
Max. leakage current (IL max) with the isolator open (isolated state): 15mA
Max. series impedance with the isolator closed (Zc max): 170 m ohm at 15Vdc
These sensors have been Independently tested and certified as shown in the table.
EN54-5 states that Class A1 has a maximum application temperature of 50
B has a maximum application temperature of 65
WIRING GUIDE
Refer to the installation instructions supplied with the plug-in sensor bases for wiring de-
tails. All bases are provided with terminals for power and an optional Remote Indicator.
Note 1: All wiring must conform to applicable local and national codes and regulations.
Note 2: Verify that all sensor bases are installed and that polarity of the wiring is correct
at each base.
Disconnect loop power before installing sensors. Notify proper authorities.
SENSOR INSTALLATION
1. Set the sensor address (see figure 1) by turning the two rotary switches on the
underside of the sensor, selecting a number between 01 and 159. (Note: The
number of addresses available will be dependent on panel capability, check the panel
documentation for information on this). Record the address on the label attached
to the base.
Figure 1: Rotary Address Switches
X 10
2. Insert the sensor into the base and rotate it clockwise until it locks into place.
3. After all the sensors have been installed, apply power to the system.
4. Test the sensor as described under TESTING.
5. Reset the sensor by communication command from the panel.
Tamper-Resistance.
These sensors includes a feature that, when activated, prevents removal of the sensor
from the base without the use of a tool. Refer to the installation instructions for the
sensor base for details of how to use this feature.
H200-203-00
Honeywell Building Solutions, Honeywell House, Arlington Business Park, Bracknell, Berkshire, RG12 1EB, UK
TC808E(I)S1028 TC808E(I)S1002 TC808E(I)S1051
C and rate-of-rise (10
o
C temperature sensing (Class A1S).
o
C high temperature sensing
o
visible sensor indication (operation
o
15 to 32 VDC (15 to 28 for 'I' isolated models)
C
o
C
o
190 µA @24 V and 25
C
o
add 50 µA for 'I' Isolated
add 3.5 mA @ 24 V and 25
C
o
10% to 93% Relative Humidity, Non-Condensing
C.
o
WARNING
X 1
DOP-IFD170 TC808ES1028 EN54-5: 2000 Class A1R
DOP-IFD171 TC808EIS1028 EN54-5: 2000 Class A1R,
DOP-IFD172 TC808ES1002 EN54-5: 2000 Class A1S
DOP-IFD173 TC808EIS1002 EN54-5: 2000 Class A1S,
0786
DOP-IFD174 TC808ES1051 EN54-5: 2000 Class BS
09
DOP-IFD175 TC808EIS1051 EN54-5: 2000 Class BS,
Honeywell House, Arlington Business Park, Bracknell, Berkshire, RG12 1EB, UK
Dust covers help to protect units during shipping and when first installed.
They are not intended to provide complete protection against contamination
therefore sensors should be removed before construction, major re-decora-
tion or other dust producing work is started. Dust covers must be removed
MAINTENANCE
Before cleaning, disable the system to prevent unwanted alarms:
C/minute)
o
1. Remove the sensor to be cleaned from the system.
2 Use a vacuum cleaner and/or clean, compressed air to remove dust and debris from
the thermistor and sensor cover.
3. Replace the sensor into the base.
4. When all sensors have been cleaned, restore power to the loop and test the sensor(s)
as described under TESTING.
TESTING
Sensors must be tested after installation and following periodic maintenance. Disable
the zone or system undergoing maintenance to prevent unwanted alarms.
Test the sensors as follows:
Magnet Method
1. Test the sensor by positioning the test magnet (model M02-24-optional) against
the sensor body approximately 2cm from LED 1, indicated by a mark on the sensor
cover as shown in figure 2.
2. Both LED's on the sensor should latch into alarm within 30 seconds, activating the
control panel.
Figure 2: Test Magnet Position
C, Class
o
Control Panel Method
1. Test the sensitivity from the system control panel.
Direct Heat Method (Hair dryer of 1000-1500 watts).
1. Direct the heat toward the sensor from its side. Hold the heat source about 15 cm
away to prevent damage to the cover during testing.
2. The LEDs on the sensor should light when the temperature at the sensor reaches
58°C/78°C (dependent on the model being tested).
3. Reset the sensor at the system control panel.
After completion of the test notify the proper authorities that the system is operational.
Fire sensors must be used in conjunction with compatible equipment.
Heat sensors are designed to protect property, not life. They do not provide early
warning of fire and cannot detect smoke, gas, combustion particles or flame.
Heat sensors do not always detect fires because the fire may be a slow smouldering,
low-heat type (producing smoke) or because they may not be near where the fire oc-
curs, or because the heat of the fire may bypass them. Consideration must be made
of the environment when selecting heat sensors.
Fire sensors cannot last forever. Fire sensors contain electronic parts. Even though
sensors are made to last over 10 years, any of these parts could fail at any time.
Therefore, test your fire detection system at least semi-annually. Taking care of the fire
detection system you have installed will significantly reduce your product liability risks.
Honeywell Control Systems Ltd
I 56- 3425- 003
CAUTION
before system can be made operational.
Test Magnet
Mark on Cover
LED 1
WARNING
LIMITATIONS OF THERMAL SENSORS
EN54-17: 2005
EN54-17: 2005
EN54-17: 2005
LED 2
I56-3425-003

Werbung

loading

Inhaltszusammenfassung für Honeywell TC808 Serie

  • Seite 1 Refer to the installation instructions for the sensor base for details of how to use this feature. H200-203-00 Honeywell Building Solutions, Honeywell House, Arlington Business Park, Bracknell, Berkshire, RG12 1EB, UK I56-3425-003...
  • Seite 2 5. Resettare il sensore mediante un comando di comunicazione impartito dal pannello. mesi. La corretta manutenzione del sistema di rilevazione di incendio installato riduce significativamente i rischi di responsabilità. H200-203-00 Honeywell Building Solutions, Honeywell House, Arlington Business Park, Bracknell, Berkshire, RG12 1EB, UK I56-3425-003...
  • Seite 3 DESCRIPCIÓN GENERAL los sensores deben extraerse antes de iniciar cualquier tipo de obra, Los sensores térmicos analógicos TC808 Serie utilizan un único circuito de detección remodelación u otra actividad que genere polvo. Las fundas protectoras con termistor para proporcionar un aviso incipiente del fuego en desarrollo con deben extraerse antes de la puesta en marcha del sistema.
  • Seite 4 4. Prüfen Sie den Melder wie im Abschnitt PRÜFUNG beschrieben. Inspektionen des Brandmeldesystems reduzieren erheblich das Produkthaftungsrisiko. 5. Setzen Sie den Melder an der Brandmelderzentrale zurück (Reset). H200-203-00 Honeywell Building Solutions, Honeywell House, Arlington Business Park, Bracknell, Berkshire, RG12 1EB, UK I56-3425-003...

Diese Anleitung auch für:

Tc808es1028Tc808eis1028Tc808es1002Tc808eis1002Tc808es1051Tc808eis1051