2. Explosion protection and approvals
Regulating and control components
type 07-7331-..../....
ATEX
Test certificate
Ex protection type
IECEx
Test certificate
Ex protection type

Special conditions

(1) The regulating and control components must be installed in an
enclosure which corresponds to the requirements of a
recognised class of protection in accordance with
EN 60 079-0, Section 1.2.
(2) When installing in an enclosure with an increased
safety class of protection "e" in accordance with
EN 60079-7:2007, the clearance and creep age distances set
out under Section 4.3, Section 4.4 and Table 1 must be
complied with.
(3) The component can be used in Group I and II because the
requirements of the standard are identical in this case.
CSA
Test certificate
INMETRO
Test certificate
Customs Union Russia (EAC)
Test certificate
Further certificates
Max-Eyth-Straße 16
DE
97980 Bad Mergentheim
GmbH
Deutschland
MODEX
PROFIBUS-Interface 4 x RTD in Ex
PTB 97 ATEX 1066 U
TÜV 01 ATEX 1668
II 2(1) G Ex db e [ia Ga] IIC/IIB Gb
I M2 Ex db e [ia Ma] I Mb
PTB 11.0082U
Ex db e IIC Gb
Ex db e I Mb
2011-2484303U
UL-BR 13.0397U
RU C-DE.BH02.B.00005
-
www.bartec.de
Tel.: +49 7931 597-0
Fax: +49 7931 597-119
Regulating and control components
i
EU Conformity
ATEX Directive
RoHS Directive
EMC Directive 2014/30/EU
Enclosure protection class
Product labelling
Safety Datas
Type 07-7331-2307/0000
U
= 7,2V
0
I
= 6mA
0
P
= 11mW
0
Characteristic: linear
The effective internal inductances and capacitances are negligibly
small.
The maximum permissible values for the external inductance L
and the external capacitance C
Ex ia IIC
L
C
Ex ia IIB/IIIB/IIIC
L
C
Further value pairs can be made available after consultation with
BARTEC.
info@bartec.de
Vorbehalt
www.bartec.de
Typ 07-7331-2307/0000
2014/34/EU
2011/65/EU
2014/30/EU
EN 60529:1991+A1:2000+A2:2013
0044
are given in the following table:
0
100
10
1,0
100
0
mH
mH
mH
µH
0,99
1,3
1,9
3,4
0
µF
µF
µF
µF
100
10
1,0
100
0
mH
mH
mH
µH
4,9
6,6
11
20
0
µF
µF
µF
µF
Technische Änderungen behalten wir uns vor.
Änderungen, Irrtümer und Druckfehler begründen
keinen Anspruch auf Schadensersatz.
0
10
2
µH
µH
7,6
13,5
µF
µF
10
2
µH
µH
60
240
µF
µF
2/18