Honeywell EEM230-D-M Montage- Und Bedienungsanleitung Seite 2

32 a-wirkenergiezähler 1-phasig mit m-bus schnittstelle
Vorschau ausblenden Andere Handbücher für EEM230-D-M:

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Value information field (VIF)
Provides information on multiplier and the unit of the following data block
Value information field extension (VIFE)
Detailed information on multiplier and the unit of the following data block
Data information field (DIF)
Specifies how the data should be interpreted by the master in terms of length and encoding
Data information field extension (DIFE)
Provides information on the tariff or subunits of the following data block
Reading meter
Query:
REQ_UD2
Response:
RSP_UD (see Telegram structure)
Telegram structure
0x68
0x38
0x38
0x68
0x08
PAdr
0x72
ID
02
ACC
STAT
0
0
0x8c
0x10
0x04
0x04
Epa
0x02
0xFD
0xC9
0xFF
0x01
V
0xFF
0x01
I
0x02
0xAC
0xFF
0x01
P
0xFF
0x01
Pr
CSum
0x16
Variable at 1, 2 or 4 bytes
Byte
Content
Type
Description
23 - 26
Eto=x
4 b. BCD
Energy total
30 - 33
Epa=x
4 b. BCD
Energy partial
39 - 40
V=x
2b. Integer
Voltage
46 - 47
I=x
2b. Integer
Current
52 - 53
P=x
2b. Integer
Power
59 - 60
Pr=x
2b. Integer
Reactive Power
Unit with multiplier
Unit with multiplier
I I
(Current)
(Current)
U U
(Voltage)
(Voltage)
P P
(Power)
(Power)
active
active
P P
(Reactive Power)
(Reactive Power)
reactive
reactive
E E
(Consumption)
(Consumption)
Assembly and operating instructions EEM230-D-M
32 A Single Phase active power energy meter with M-Bus interface, Pic. 1
Description
Energy meter with M-Bus interface enables the reading
of all relevant data like meter reading, electricity, voltage,
power (active and reactive).
Technical data
Connection
Pic. 2
diagram
Dimensions
Pic. 3
Accuracy class
B according to EN50470-3,
1 according to IEC62053-21
Reference, Maxi-
I
= 5 A, I
ref
0xEE
0x21
DEV
mum, initial current
operating voltage
230 V
Eto
0x8c
0x11
Tolerance −20%/+15%
0x02
0xFD
0xDB
Counting range
00 000,00...999 999,9 kWh
Connections
Conductor cross-section max. 6 mm
0x82
0x40
0xAC
Main circuit
screwdriver pozi no. 1, slot no. 1,
torque 1,2 Nm
Connections
Conductor cross-section max. 2,5 mm
Control circuit
screwdriver pozi no. 0, slot no. 1,
torque 0,5 Nm
Operating
−25...+55°C (noncondensing
temperature
according standard EN50470)
Environment
Mechanical M2
Electromagnetic E2
Indicating elements
(Pic. 4)
T total (kWh)
Indicates the total consumption
T part (kWh)
Indicates the partial consumption.
This value can be reset
P (kW)
Indicates the instantaneous power
U (V)
Indicates the voltage
I (A)
Indicates the current
2000 pulses/kWh
Pulsates according to the amount
of used power. Error indication
0.1
0.1
[ A ]
[ A ]
(line 1L/2L inverted) with pulse of
600/600 ms.
1 1
[ V ]
[ V ]
0.01
0.01
[ kW ]
[ kW ]
0.01
0.01
[ kVAR ]
[ kVAR ]
0.01
0.01
[ kWh ]
[ kWh ]
Made in Romania
4 319 5161 0 D
English
Notes before connecting
In order to avoid moisture in the meter due to condensate
build-up, acclimatise the meter at room temperature for
about half an hour before connecting.
Attention!
These devices must only be installed by a professional
electrician, otherwise there is the risk of fire or the risk of
an electric shock.
Operation of the LCD display
See page with LCD menu navigation.
= 32 A, I
20 mA
max
st =
, 50 Hz
AC
Installation instructions
The energy meter can be attached to a 35 mm rail
2
,
(EN60715TH35).
The meter can be used only in installation cabinets.
2
,
Declaration of Conformity CE
We, Honeywell Technologies Sàrl, 1180 Rolle (Switzer-
land), herewith declare, on our own responsibility that
the product:
EEM230-D-M-MID
which this certificate refer to, are in accordance with the
directive 2014/32/EU (MID) and the following standards:
EN50470 parts 1 and 3 (electronic meter), of
October 2006.
ESD on equipment side: 13 kV.
■ Directive 2014/30/EG (EMC)
■ Directive 2014/35/EG (LVD)
Conformity Assessment Body:
METAS-Cert, Nr. 1259
CH-3003 Bern-Wabern
Givisiez, February 2022
Signed: Maarit White, EMEA Quality Leader - BMS
UK Importer Address:
Honeywell Building Technologies
Building 5 Carlton Park
King Edward Avenue
Narborough, Leicester LE19 3EQ
2022-03-04
Subject to change without notice
Technical data M-Bus
Bus system
M-Bus
Standard
EN13757
Bus length
According to M-Bus specification
Transmission rates
300, 2400, 9600 Bd (factory setting: 2400 Bd).
The transmission rate can be changed via display/M-Bus.
Response time
Write: up to 60 ms
(System response)
Read: up to 60 ms
Data transfer
■ When reading out the values, all values are transferred in a telegram.
■ It supports the following telegrams:
• Initialisation
SND_NKE
Response: ACK
• Reading meter
REQ_UD2
Response: RSP_UD
• Changing primary address
SND_UD
Response: ACK
• Reset T
SND_UD
Response: ACK
part
• Slave selection for secondary addressing
SND_UD
Response: ACK
• The transmission rate is changeable
SND_UD
Response: ACK
( Further information you will find on the website www.sbc-support.com/en/documents/datasheets-to-products
under the document PP26-587)
■ The device does not respond to unknown queries.
■ The device has a voltage monitor. In the case of a power failure, all the registers in the EEPROM are saved.
Changing the M-Bus primary address
■ In the menu, go for «U»
■ Push long (≥ 3 sec)
«Adr ...»
■ In the following menu:
push short
M-Bus address +1,
push long
M-Bus address +10
■ When the desired address is set, wait until the main display appears again.
Secondary addressing
■ It is possible to communicate with the energy meter using the secondary address, according to EN13757
■ The use of Wild Cards is possible
Changing the baud rate:
Variant 1 (local keys and LCD):
■ In order to change the M-Bus baud rate, hold down
touch for 3 sec
■ In the following menu,
changes the baud rate from 300 to 9600 baud and 2400
■ When the desired M-Bus baud rate is set, wait until the main display appears again
Variante 2 (using M-Bus):
■ Send:
9600
Telegram:
0x68
0x03
0x03
0x68
0x43
2400
Telegram:
0x68
0x03
0x03
0x68
0x43
300
Telegram:
0x68
0x03
0x03
0x68
0x43
■ Response:
0xE5 (sent with the former baud rate)
■ A M-Bus master must communicate within 10 minutes to the M-Bus slave on the new baud rate to validate and save
the baud rate change permanent (EN13757-3).
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16,
Switzerland by its Authorized Representative:
Saia-Burgess Controls AG
Route Jo-Siffert 4
1762 Givisiez / Switzerland
Phone
+41 26 580 30 00
Fax
+41 26 580 34 99
Subject to change without notice.