Herunterladen Inhalt Inhalt Diese Seite drucken

Installing The Refrigerant Piping - Mitsubishi Electric CITY MULTI PCFY-P VKM-E-Serie Installationshandbuch

Vorschau ausblenden Andere Handbücher für CITY MULTI PCFY-P VKM-E-Serie:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 8
3. Installing the indoor unit
Fig. 3-6

4. Installing the refrigerant piping

45°±2°
Fig. 4-1
B Refrigerant pipe sizes & Flare nut tightening torque
R407C or R22
Liquid pipe
Tightening
Pipe size
torque
(mm)
(N.m)
P40
ODø6.35 (1/4")
14 - 18
P63
ODø9.52 (3/8")
34 - 42
P100/125
ODø9.52 (3/8")
34 - 42
* Flare nut ø19.05 (purchased locally): Gas pipe of P100, P125 (R407C or R22).
Fig. 4-2
4
All manuals and user guides at all-guides.com
7~12
Gas pipe
Tightening
Pipe size
Pipe size
torque
(mm)
(mm)
(N.m)
ODø12.7 (1/2")
49 - 61
ODø6.35 (1/4")
ODø15.88 (5/8")
68 - 82
ODø9.52 (3/8")
ODø19.05 (3/4")
68 - 82*
ODø9.52 (3/8")
2) Installing the suspending bracket fi rst onto the ceiling (Fig. 3-6)
Installing procedures
1. Remove the suspending brackets and U-shaped washers from the unit.
2. Adjust the suspending bracket holding bolts on the unit.
3. Attach the suspending brackets to the suspending bolts.
4. Check that the suspending brackets are horizontal (front and rear/right and left).
5. Set (hook) the unit to the suspending brackets.
6. Tighten fi xed bolts of the suspending brackets.
w Be sure to install the U-shaped washers.
A Suspending bracket holding bolt
B Unit
C U-shaped washer
D Suspending bolt
E Washer 1
F Double nuts
4.1. Connecting pipes (Fig. 4-1)
When commercially available copper pipes are used, wrap liquid and gas pipes
with commercially available insulation materials (heat-resistant to 100 °C or
more, thickness of 12 mm or more).
The indoor parts of the drain pipe should be wrapped with polyethylene foam
insulation materials (specifi c gravity of 0.03, thickness of 9 mm or more).
Apply thin layer of refrigerant oil to pipe and joint seating surface before tighten-
ing fl are nut.
Use two wrenches to tighten piping connections.
Use refrigerant piping insulation provided to insulate indoor unit connections.
Insulate carefully.
A Flare cutting dimensions
Copper pipe O.D.
Flare dimensions
(mm)
øA dimensions (mm)
ø6.35
8.7 - 9.1
ø9.52
12.8 - 13.2
ø12.7
16.2 - 16.6
ø15.88
19.3 - 19.7
ø19.05
22.9 - 23.3
R410A
Liquid pipe
Gas pipe
Tightening
Pipe size
torque
(mm)
(N.m)
14 - 18
ODø12.7 (1/2")
34 - 42
ODø15.88 (5/8")
34 - 42
ODø15.88 (5/8")
C Apply refrigerating machine oil over the entire fl are seat surface.
4.2. Indoor unit (Fig. 4-2)
Installing procedures
1. Slide the supplied pipe cover 2 over the gas tubing until it is pressed against the
sheet metal inside the unit.
2. Slide the provided pipe cover 3 over the liquid tubing until it is pressed against
the sheet metal inside the unit.
3. Tighten the pipe covers 2 and 3 at the both ends (20 mm) with the supplied
bands 4.
A Gas tubing
E Pipe cover 3
B Liquid tubing
F Press the pipe cover against the sheet metal.
C Band 4
G Refrigerant tubing heat insulating material
D Pipe cover 2
(mm)
G
P40
882 - 887
P63
1202 - 1207
P100, P125
1522 - 1527
Flare nut O.D.
Tightening
Liquid pipe
Gas pipe
torque
(mm)
(mm)
(N.m)
49 - 61
17
26
68 - 82
22
29
68 - 82
22
29

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis