Connection of an analogue sensor with intrinsic supply
analogue module
I+
C1 ... 4 (AC2216)
V1 ... 4 (AC2217)
0V
I-
Parameter setting of the analogue modules
Parameter bit/
Designation
P0
filter
P1, P2
channel activation
P3
periphery fault
All manuals and user guides at all-guides.com
sensor with
intrinsic supply
+
-
PELV supply
without ground
connection
Description
1*
50 Hz filter in the
A/D converter active
0
60 Hz filter in the
A/D converter active
parameter bit
P1
P2
0
0
0
1
1
0
1
1
*
1
periphery fault indication active
0
periphery fault indication not active
A sensor with intrinsic supply is
connected via the terminals
C1...4
(AC2216)
(AC2217) and 0V.
The 50 Hz filter applies
to the whole of Europe
analogue channel
1
2
on
off
on
on
on
on
on
on
- 13 -
or
Comments
3
4
off
off
off
off
on
off
on
on
* default