DC=
DC= Variant MC4
Eco 50-3-D
String
each max. 12 A
PV1 / PV2
each max. 75 A
PV1 + PV2
max. 87.5 A
50-3-D
String
each max. 12 A
PV1 / PV2 / PV3
36A / 36A / 72A
PV1 + PV2 + PV 3 max. 134 A
DC= Variant MC4 FUSES
Fronius Tauro Eco 50-3-D
Fronius Tauro Eco 99-3-D / 100-3-D
F1.1 - F2.7
DC= FUSE CHANGE
Max. PV array to earth capacitance (nF)
Tauro 50-3-D /
Tauro 50-3-P /
Tauro Eco 50-3-D /
Tauro Eco 50-3-P
Tauro Eco 99-3-D /
Tauro Eco 99-3-P
Tauro Eco 100-3-D /
Tauro Eco 100-3-P
Eco 99-3-D / Eco 100-3-D
String Input
each max. 12 A
PV1 / PV2 / PV3
each max. 75 A
PV1 + PV2 + PV3
max. 175 A
Max. short-circuit current
(I
PV = I
max): 18 A
SC
SC
Fronius Tauro Eco 99-3-D / 100-3-D
F3.1 - F3.8
Split strings evenly
on all input sections
10000 nF
19998 nF
20000 nF
19
Spread strings evenly
on all input sections
PV 1.1+
Fronius Tauro 50-3-D
F1.1 - F3.7
PV 1.1-