Analog input 1 can be used as a voltage input or as a current input.
Jumper settings
Analog inputs 2 and 3 can also be used as digital inputs. The switching
threshold is 8 V.
Switchover is made via jumpers on the lower section of the board. The
assignment is shown in the following table:
Table 4-3
Siemens AG 477 791 4070 76 J AA-74
SIMOVERT MASTERDRIVES
All manuals and user guides at all-guides.com
Connector
X486
Digital/analog input switchover at AI2
Jumper 1 + 2
Digital input
Jumper 2 + 3
Analog input
X487
Digital/analog input switchover at AI3
Jumper 1 + 2
Digital input
Jumper 2 + 3
Analog input
X488
Current/voltage input switchover at AI1P, AI1N
Jumper 1 + 2
Current input
Jumper 2 + 3
Voltage input
Jumper settings
Operating Instructions
Connecting-up
Significance
4-5