6 Settings motor current monitoring
The current monitoring function monitors the motor current. If the motor
current is higher than the pre-set value, an error is reported and the actuator
will remain in place. The setting is done via the left BCD switch marked
"CurrentMon." on the PCB.
BCD
EA25
0
25
1
100
2
150
3
200
4
250
5
300
6
400
7
500
8
600
9 (factory setting)
700
7 Error message
An error can trigger the following:
 The 7-segment display on the main board illuminates; see illustration
below. If the positioner PCB is installed, the respective LED lights up red on
the BCD switch, if its set value is exceeded.
 The ready-to-operate signal will be off (terminals 5,6 NO contact)
 LED flashes yellow (except in case of power outage)
Assignment of error codes for error messages
If the positioner PCB is installed, the following error codes can be displayed:
Error code
Description
Setpoint error

Actual value error

Setpoint reversed polarity

Actual value reversed

polarity
Setpoint short circuit

Actual value short circuit

Actuator has run into

engine current limit
* If the feedback is not connected the error LED will show an actual value error. This can
be avoided by placing a resistor (supplied) between terminal 5 and 6 of the positioner.
Remove the resistor to use the feedback.
For further error codes of the main board, see instruction manual of the electric actuator
type EA 25-250.
EA45
EA120
EA250
25
50
50
300
300
400
350
400
500
400
500
600
450
600
700
500
700
800
600
800
1000
700
900
1200
900
1000
1500
1100
1200
1800
Signal „Ready-
EA response
to-operate"
None
None
None
None
None
None
No
Stops
Acknowledge error message
Check the cause of fault, if necessary, carry out relevant maintenance.
The message can be eliminated while the supply voltage is still connected
or the actuator is briefly disconnected from the mains voltage (does not
work with cycle monitoring).
Error can be acknowledged via the „SET" button on the main board.