G
®
AERASGARD
RCO
Humidity table
MR: 0...100 % r. H.
%
U
I
A
A
r.H.
in V
in mA
0
0
4.0
5
0.5
4.8
10
1.0
5.6
15
1.5
6.4
20
2.0
7.2
25
2.5
8.0
30
3.0
8.8
35
3.5
9.6
40
4.0
10.4
45
4.5
11.2
Continued at the right ...
AERASGARD
®
RCO
- W
2
®
AERASGARD
RLQ - CO
2
®
AERASGARD
RFTM - LQ - CO
Type ⁄ WG02
RCO
- W
2
R C O 2 -W- D I S P L AY
RLQ - CO
2
R L Q - C O 2 -W
R L Q - C O 2 -W- D I S P L AY
RFTM - CO
2
R F T M - C O 2 -W
R F T M - C O 2 -W D I S P L AY
RFTM - LQ - CO
2
R F T M - L Q - C O 2 -W
R F T M - L Q - C O 2 -W D I S P L AY 0...100 % r.H.
Note:
- W ⁄ RLQ - CO
- W ⁄ RFTM - LQ - CO
2
2
%
U
A
r.H.
in V
in mA
50
5.0
12.0
55
5.5
12.8
60
6.0
13.6
65
6.5
14.4
70
7.0
15.2
75
7.5
16.0
80
8.0
16.8
85
8.5
17.6
90
9.0
18.4
95
9.5
19.2
100
10.0
20.0
Room CO
sensors and measuring transducers, Deluxe
2
- W
Room air quality (VOC) and CO
Multifunctional room sensors and measuring transducers, Deluxe
2
Measuring Range
Humidity
Temperature
–
–
–
–
–
–
0...100 % r.H.
0...+50 °C
0...100 % r.H.
0...+50 °C
0...100 % r.H.
0...+50 °C
0...+50 °C
This unit must not be used as safety-relevant device!
2
Temperature table
MR: 0...+50 °C
I
°C
U
A
in V
0
5
1.0
10
2.0
15
3.0
20
4.0
25
5.0
30
6.0
35
7.0
40
8.0
45
9.0
50
10.0
sensors and measuring transducers, Deluxe
2
CO
VOC
2
(switchable)
0...2000 ⁄ 5000 ppm
–
(switchable)
0...2000 ⁄ 5000 ppm
0...100 %
0...2000 ⁄ 5000 ppm
0...100 %
(switchable)
0...2000 ⁄ 5000 ppm
–
0...2000 ⁄ 5000 ppm
–
(switchable)
0...2000 ⁄ 5000 ppm
0...100 %
0...2000 ⁄ 5000 ppm
0...100 %
11
I
A
A
in mA
0
4.0
5.6
7.2
8.8
10.4
12.0
13.6
15.2
16.8
18.4
20.0
*
Equipment and enclosure:
W = 1x changeover contact
B2 = enclosure Baldur 2
*
Item No.
Display
W, B2
■
1501-61B0-7321-200
W, B2
1501-61B1-7301-200
W, B2
■
1501-61B1-7321-200
W, B2
1501-61B6-7301-200
W, B2
■
1501-61B6-7321-200
W, B2
1501-61B8-7301-200
W, B2
■
1501-61B8-7321-200
Rev. 2017 - V25 GB