Installation

Intended use
The manual call point FDM365-RP is for manual alarm
activation in the event of a fire.
The manual call point FDM365-RP (Fig. 1) consists of a
housing cover (1) and a switching unit (2).
The back boxes FDMH295-R and FDMH295-S are
available as an option for surface mounting.
A protective cover FDMC295 (accessories) can be
installed for the manual call point to prevent unintentional
alarm activation.
Secure the manual call point at a height of 0.9...1.6 m on
an even surface.
Observe the country-specific regulations for the
exact installation height!
Preparation and installation
1. Insert the key (4) into the manual call point FDM365-RP
from below and pull the housing cover (1) forward and
away from the switching unit (2) (as in Fig. 3).
If you are using back box FDMH295-R, the following
additional measures are necessary:
2. Determine the positions of the entry openings in the
back box.
3. Mark the drill hole(s) with Ø max. 20 mm on the back
box according to the drilling jig (Fig. 5).
4. Clamp the back box in a bench vice.
CAUTION
Improper use of tools
Danger of injury
Observe the tool manufacturer's safety notices.
5. Drill the entry opening(s) (Fig. 6).
2
Connecting the switching unit to the electricity
1. If the detector line cables are shielded (Fig. 7), connect
the shielding to a connection terminal DBZ1190-AB
(accessories). The shielding must not touch any other
potentials or metal parts in the device.
2. Connect the detector line (Fig. 7).
Note the positive and negative poles.
Only connect one wire per terminal. This is the
only way to ensure the connection is failure-free
for the entire service life of the device.
3. Install the switching unit (2) in a recessed box
(FDM365) or in the back box (3). Pay attention to the
feed line when inserting the switching unit (2) into a
recessed box or the back box. Avoid crushing the feed
line.
4. Install the housing cover (1) on the switching unit (2).
Installation of protective cover FDMC295
· Engage the protective cover in the two recesses in the
housing cover (see Fig. 9).
Testing
1. Insert the key (4) in the detector so that the insert
moves (Fig. 8).
The detector is triggered.
è
2. To arm the manual call point, pull out the key again.
The insert is straight and the manual call point has
è
been set.
WARNING
Deactivating the manual call points prevents
alarms from being forwarded
The alarm is not triggered.
Label deactivated or inoperable manual call points
as "NOT IN USE".
You will find more information in
document A6V11706079.