Herunterladen Diese Seite drucken

Hengstler tico 731.2 Betriebsanleitung Seite 2

Lcd-zähler mit dc- versorgung

Werbung

Operating instructions tico 731.2
- DC powered LCD- Counter
The tico 731.2 is a DC powered LCD- counter with programmable
count input for contact or edge triggering. The following versions are
available:
Totalizer:
Tachometer (1/min)
Time counter (HHHH:MM:SS)
Time counter (HHHHHHH.HH):
or with plug in screw terminal e. g. 0 731 201 S
1. Programming of the COUNT- Input (all versions)
In order to match your application, the COUNT-Input can be
programmed for high speed (7,5kHz) or low speed counting (30 Hz
attenuated). Positive or negative edge is programmable as well.
NOTE:
The counter leaves the factory with the default value HI PNP
(f
7,5 kHz and positive edge triggered) and unlocked key.
max
To change the count input configuration:
Sach-Nr. 2 731 021; Version 1160215AK
standard
special
0 731 201
0 731 721
0 731 202
0 731 722
0 731 203
0 731 723
0 731 204
0 731 724
HENGSTLER
2. Totalizer version (0 731 201)
Terminal 4 "RESET or Tacho HOLD" is defined as the Reset- Input.
3. Tachometer version (0 731 202)
The tachometer operates via the gate measuring method. Within the
measuring time of 6 sec, the incoming pulses are counted and recal-
culated in order to display 1/min.
The Terminal 4 "RESET or Tacho- HOLD" is defined as the HOLD-Input
(as long as this Input is active, the actual value in the display is
frozen.)
4. Time counters versions (0 731 203 and 204)
the time counters will count as long as the Count- Input (3) is active
(this can be a low or a high signal according to programming in
Chapter 1).
Terminal 4 "RESET or Tacho-HOLD" is defined as RESET-Input.
5. Terminal connection
Totalizer, Tacho, Time counters
6. Specifications
Power Supply
Current consumption
Data retention
Display
Count input
active edge
Count frequency
Amplitude threshold
Reset or input or
tacho hold
Key reset
Keylock
Mounting
Front dimension
Panel cut- out
Panel thickness
Product depth
Protection class
Operating temperature
Storage temperature
General rating
Protection class
Overvoltage
Contamination
Terminal 1 and 2; 12..24 VDC
Tolerances: +20 -5%
5mA, external overvoltage
ext. fuse max. 3A
non volatile RAM (NV), >10 years
LCD, 8-digit,7mm
Terminal 3 "Count"
programmable: NPN: negative
(e.g) Contact to ground OV) or
PNP: positive signal
pulse length: min 70µs or
min 17 ms (if attenuated to 30 Hz)
programmable:
"HI" 7,5 kHz or "LO" 30 Hz
(attenuated for Contacts)
< 0,7V and > 5V, max 30 VDC
at NPN input < 0.5V and > 5V,
max. 30VDC
Reset with a negative edge on
"RESET", (Terminal 4 bridge to
Ground, 0V)
pulse length: min 17 ms
(attenuated to 30 Hz)
press front key shortly
programmable see chapter 1
Frontpanel mounted with clamping
frame
DIN 48 mm x 24 mm
+0,6
+0,3
45
mm x 22
mm
max. 14 mm
32 mm
front side IP 54
-10
C to +50
C
-20
C to +60
C
DIN EN 61010 - 1
according to class II
category II
level 2
Seite 2 von 7

Werbung

loading