Short circuit isolator module

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

FIGURE 1: MODULE MOUNTING METHODS
M200E-SMB Surface Mount Box
SURFACE MOUNT BOX BASE IS
AFFIXED TO MOUNTING SURFACE,
THEN THE MODULE AND COVER
ARE SCREWED ONTO THE
BASE USING THE TWO SCREWS
SUPPLIED.
M200E-DIN DIN Rail Bracket
PUSH MODULE
INTO ADAPTOR
BRACKET UNTIL IT
CLIPS INTO PLACE.
M200E-PMB Panel Mount Bracket
ADAPTOR BRACKET IS MOUNTED
DIRECTLY INTO PANEL USING 2 X
M4 PAN HEAD SCREWS.
MODULE IS PUSHED INTO
ADAPTOR UNTIL IT CLIPS INTO
PLACE.
M200XE ISOLATOR MODULE WIRING
LOOP OUTPUT -
LOOP OUTPUT+
LOOP INPUT -
LOOP INPUT +
D200-90-00
INSTALLATION INSTRUCTIONS:
SHORT CIRCUIT ISOLATOR MODULE
TOP
BOTTOM
LOCATE TOP CLIP OVER DIN RAIL
AND ROTATE BOTTOM DOWN TO
CLIP INTO PLACE.
TO REMOVE, LIFT UP, THEN ROTATE
TOP AWAY FROM THE RAIL.
M200XE
A
Pittway Tecnologica S.r.l, Via Caboto 19/3, 34147 Trieste, Italy
M200XE
This manual is intended as a quick reference installation guide. Please
refer to the control panel manufacturers installation manual for detailed
system information.
SPECIFICATIONS
COVER
Operating Voltage Range:
Maximum Standby Current (μA): 200μA at 24VDC
Maximum continuous current with isolator closed (Ic max): 0.9A (V ≤ 28V)
Maximum continuous current with isolator closed (Ic max): 0.8A (28V < V ≤ 29V)
MODULE
Maximum switching current with isolator closed (Is max): 0.95A (V ≤ 28V)
Maximum switching current with isolator closed (Is max): 0.85A (28V < V ≤ 29V)
Max. leakage current (IL max) with isolator open (isolated state): 15mA
Max. series impedance with isolator closed (Zc max): 170 m ohm at 15Vdc
BASE BOX
Operating Temperature:
Humidity:
Module Dimensions:
Surface Mount Box Dimensions: 132mm(H) x 137mm(W) x 40mm(D)
Weight (including terminal blocks): 62 g
Weight (Module in M200E-SMB): 200 g
Maximum Wire Gauge:
INSTALLATION
Note: These modules must only be connected to control panels using
compatible proprietary analogue addressable communication protocols
for monitoring and control. The M200XE itself is not controllable by loop
communication protocols.
Disconnect loop power before installing modules or sensors
M200+ series modules can be mounted in several ways (See figure 1):
1. An M200E-SMB custom low profile surface-mounting box.
2. An M200E-DIN Adaptor allows mounting onto standard 35mm x
7.5mm "Top Hat" DIN rail.
3. An M200E-PMB Panel Mount Bracket allows the module to be
mounted directly into a panel.
Wiring to all series M200+ modules is via plug in type terminals capable
of supporting conductors up to 2.5mm².
M200XE SHORT CIRCUIT ISOLATOR MODULE
Provides monitoring and isolation of short circuits on the loop. When a
short circuit is detected, or if power is removed from the module, a 2.2KΩ
resistor is placed into the positive side of the loop to provide isolation of
the fault.
The M200XE has a bi-colour (Green/Yellow) LED. In normal conditions,
the LED will blink green each 3 seconds. When a short circuit is detected,
either on the input or the output side, the LED will be be lit steady yellow
when wired on the loop. If wired on a spur from the loop, when a short
circuit is detected the LED will be lit steady yellow if the short is after the
isolator, but not lit if the short is before the isolator.
B
C
15 to 29VDC (Min 17.5VDC to ensure LED operation)
-20°C to 60°C
5% to 95% Relative Humidity
93mm(H) x 94mm(W) x 23mm(D) (Including terminals)
2.5mm²
CAUTION
DOP-IOD040
EN54-17: 2005
Honeywell Products and Solutions Sàrl
(Trading as System Sensor Europe)
0786 17
Zone d'activités La Pièce 16
CH-1180 ROLLE, Switzerland
E N G L I S H
I 56- 1765- 011
I56-1765-011

Werbung

loading

Inhaltszusammenfassung für System Sensor M200XE

  • Seite 1 Note: These modules must only be connected to control panels using CLIPS INTO PLACE. compatible proprietary analogue addressable communication protocols for monitoring and control. The M200XE itself is not controllable by loop BOTTOM communication protocols. LOCATE TOP CLIP OVER DIN RAIL...
  • Seite 2 (negativa), sul lato positivo del loop viene posizionata una resistenza da 2,2 Kohm in modo da isolare il guasto. Il modello M200XE è dotato di un LED bicolore (Verde/Giallo). condizioni normali, il LED lampeggia a luce verde ogni 3 secondi.
  • Seite 3 ENCIMA DEL RIEL DIN Y GIRE LA utilizando protocolos de comunicaciones analógicas direccionables PARTE INFERIOR HACIA ABAJO compatibles y exclusivos para supervisión y control. El M200XE en sí no HASTA ENCAJARLA. es controlable por protocolos de comunicación en el lazo.
  • Seite 4 M200XE ISOLATORMODUL VERDRAHTUNG geschaltet und das fehlerhafte Element isoliert. Das Modul M200XE verfügt über eine zweifarbige (grün/gelb) LED. Im Normalzustand blinkt die LED alle 3 Sekunden grün auf. Ein Kurzschluss auf der Ein- oder Ausgangsseite wird mit der dauerleuchtenden gelben LED angezeigt, wenn die Verdrahtung im Ring erfolgt.