Herunterladen Inhalt Inhalt Diese Seite drucken

Normen Für Prüfungen Mit Koppelnetzwerken Der Serie Cnv 504 / Cnv 50X; Gerätemodelle - EM TEST N Serie Bedienungsanleitung

Koppelnetzwerk für surge auf signal und datenleitungen
Inhaltsverzeichnis

Werbung

EM TEST
1.
Normen für Prüfungen mit Koppelnetzwerken der Serie CNV 504 / CNV 50x
Die Koppelnetzwerke der Seie CNV504 / 50x decken die folgenden Normen ab:
- IEC 61000-4-5
- EN 50121-3-2
- IEC 61000-4-12
1.1.
Gerätemodelle
Die unten stehende Liste zeigt eine Auswahl der bei EM Test verfügbaren Koppelnetzwerke für Signal- und Da-
tenleitungen.
Standardmodelle:
CNV 504N1
4kV coupling/decoupling network for Surge and Ringwave onto 4 signal/data lines
with 40ohm via 0.5uF capacitor (as per Fig. 11, IEC 61000-4-5) and arrestor (as per Fig.12);
with 3.3uF capacitor for Ringwave (as per Fig. 9, IEC 61000-4-12);
Rated line voltage/current 50V/1A
CNV 504N1.1
4kV coupling/decoupling network for Surge and Ringwave onto 4 signal/data lines
with 40ohm via 0.5uF capacitor (as per Fig. 11, IEC 61000-4-5) and arrestor (as per Fig.12);
with 3.3uF capacitor for Ringwave (as per Fig. 9, IEC 61000-4-12);
Rated line voltage/current 50V/4A
CNV 504N1.2
4kV coupling/decoupling network for Surge and Ringwave onto 4 signal/data lines
with 40ohm via 0.5uF capacitor (as per Fig. 11, IEC 61000-4-5) (as per Fig.12);
with 3.3uF capacitor for Ringwave (as per Fig. 9, IEC 61000-4-12);
Rated line voltage/current 250V/1A
CNV 504N1.3
4kV coupling/decoupling network for Surge and Ringwave onto 4 signal/data lines
with 40ohm via 0.5uF capacitor (as per Fig. 11, IEC 61000-4-5) (as per Fig.12);
with 3.3uF capacitor for Ringwave (as per Fig. 9, IEC 61000-4-12);
Rated line voltage/current 250V/4A
CNV 504N1.4
4kV coupling network for 4 data/signal lines 50V,
via coupling capacitor and gas arrestor
(No decoupling included !!!)
CNV 504N1.5
4kV CDN for 4 data/signal lines 230V/1A,
via coupling capacitor and gas arrestor (600V)
CNV 504N1.6
4kV coupling/decoupling network for Surge and Ringwave with
40ohm via 0.5uF capacitor (asper fig.11, IEC 61000-4-5) and gas arrestor (as per Fig.12) ;
with 3.3uF capacitor for Ringwave (as per fig.9, IEC 61000-4-12);
Rated line voltage/current 250V/4A, max. 50V for tests with gas arrestor
CNV 508N1
4kV coupling/decoupling network for Surge and Ringwave onto 8 signal/data lines
with 40ohm via 0.5uF capacitor (as per Fig. 11, IEC 61000-4-5) and arrestor (as per Fig.12);
with 3.3uF capacitor for Ringwave (as per Fig. 9, IEC 61000-4-12);
Rated line voltage/current 50V/1A
CNV 508N1.1
4kV coupling/decoupling network for Surge and Ringwave onto 8 signal/data lines
with 40ohm via 0.5uF capacitor (as per Fig. 11, IEC 61000-4-5) and arrestor (as per Fig.12);
with 3.3uF capacitor for Ringwave (as per Fig. 9, IEC 61000-4-12);
Rated line voltage/current 50V/4A
CNV 504N2
7kV coupling/decoupling network for Surge and Ringwave
with 40ohm via 0.5uF capacitor (as per Fig. 11, IEC 61000-4-5) and arrestor (as per Fig.12);
with 3.3uF capacitor for Ringwave (as per Fig. 9, IEC 61000-4-12);
Rated line voltage/current 50V/1A
CNV 504N2
7kV coupling/decoupling network for Surge and Ringwave
with 40ohm via 0.5uF capacitor (as per Fig. 11, IEC 61000-4-5) and arrestor (as per Fig.12);
with 3.3uF capacitor for Ringwave (as per Fig. 9, IEC 61000-4-12);
Rated line voltage/current 250V/1A
Bedienungsanleitung
Surge 1.2/50 , 10/700
Surge CNV 504N1
Ringwave
V 1.20
CNV 504N1/N2 / 508N1/N2
4 / 24