Herunterladen Diese Seite drucken

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Addressable mimic relay board
CIOP4, CIOP8
Installation Instructions
Specification
Loop Load
Quiescent Current
Operating Loop Voltage
Outputs
Compatibility
Recommended Loop Cable Type FIRETUF, FP200, MICC
Part codes
Order code
Description
CIOP4
4 way addressable Mimic Relay Board, 4 inputs, 4 outputs
CIOP8
8 way addressable Mimic Relay Board, 4 inputs, 8 outputs
MIOP4
4 way addressable Mimic Relay Board, 4 inputs, 4 outputs
MIOP8
8 way addressable Mimic Relay Board, 4 inputs, 8 outputs
FXIOP4
4 way addressable Mimic Relay Board, 4 inputs, 4 outputs
FXIOP8
8 way addressable Mimic Relay Board, 4 inputs, 8 outputs
ZPCB2312-4
4 way addressable Mimic Relay Board, 4 inputs, 4 outputs
WITHOUT BOX
ZPCB2312-8
8 way addressable Mimic Relay Board, 4 inputs, 8 outputs
WITHOUT BOX
Physical
Order code
Dimensions
CIOP4, CIOP8
254 x 180 x 90mm 1.0kg
ZPCB2312-4,
163 x 113mm
ZPCB2312-8
Short circuit isolation
This addressable device contains an integral short circuit isolator,
which operates between the – IN terminal and the – OUT
terminal. The isolator operates in conjunction with the Eaton
Addressable Control Panel when a low parallel resistance fault of
typically 200 is present between the +VE and –VE of the
loop wiring.
Short circuit isolation data (integral with each device)
Total Loop Resistance for correct operation of short circuit isolator 50Ω (max)
Parallel Fault Resistance to be seen at the Control Panel for
isolators to open
Continuous Current allowable through isolator
Isolator Resistance in closed state
Leakage Current into direct short circuit with isolator open
Voltage at which isolator changes from open to closed or
closed to open state
Maximum switching current to isolator
Min
Nom
Max
6mA
18.5V DC
30V DC
Suitable for use with Eaton
Addressable Fire Systems
Weight
Humidity (Non condensing)
95 %RH
180g
95 %RH
200Ω (typ)
700mA (max)
0.26Ω (max)
14mA (max)
3.8V to 11V
1.5A
Addressable mimic relay board
CIOP4 and CIOP8 are 4 and 8 way soft addressing output module,
incorporating integral short circuit isolators. It is fully compatible
with the current range of Eaton analogue fire detection panels and
OEM derivative panels. It is suitable for switching low voltage (24V
DC @ 1amp maximum), via a set of non-latching relay contacts.
The flexibility of this module is further enhanced by the fact that
each output can be programmed for a range of triggers as e.g.
Disablement, Fault, Fire, test panel, test zone, Pre-alarm,
Fire Routing equipment, Fire Protecting equipment and reset with
up to 16 different trigger sources per output. The trigger source
can be Global, by Panel, by Loop, by Zone or by address.
The Logic can be an OR and AND function.
The unit has an additional 4 inputs which can initiate a Reset,
Silence, Evacuate and test function. This can be programmed
using the DF6000/CF3000 programmable Site Installer software
and downloaded using the RS232 port.
Features
4 and 8 relay versions available
Pluggable terminals for ease of wiring
Build in short circuit isolator to enhance system integrity
Unit can be soft or hard addressed
Incorporating 4 inputs Reset, Silence, Evacuate and Test
No addressing of module required (soft addressed), reduce
errors and saves time.
The relay outputs are change-over, latching, volt free contacts
which are none monitored
Loop powered , no need for an external power supply
Number of settings per output: 16
rigger types: Fire, Fault, Disablement, Test, Pre-Alarm, FRE,
FPE, Reset
Trigger source: Global, by Panel, by Loop, by Zone, by Address
Rule logic: Disjunction (OR) and Conjunction (AND)
Overview
Bank of jumper links (J10) used to select loop or RS232
Jumper link (JP2) to select RS232
Reset button: press the button to reset the Graphical
Relay Board
Test button: press the button to start test mode, the outputs
activate one at a time
Bank of jumper links to set outputs to pull up or down
There are no serviceable parts so no maintenance
procedures apply
Effective November 2019
14
0905
DoP0250
DoP0251
EN54-17:2005+AC:2007
EN54-18:2005+AC:2007

Werbung

loading

Inhaltszusammenfassung für Eaton CIOP4

  • Seite 1 DoP0251 EN54-17:2005+AC:2007 EN54-18:2005+AC:2007 Specification Addressable mimic relay board Loop Load CIOP4 and CIOP8 are 4 and 8 way soft addressing output module, Quiescent Current incorporating integral short circuit isolators. It is fully compatible Operating Loop Voltage 18.5V DC 30V DC...
  • Seite 2 Eaton © 2019 Eaton EMEA Headquarters All Rights Reserved Route de la Longeraie 7 Eaton is a registered trademark. Eaton Electrical Systems Ltd. 1110 Morges, Switzerland Wheatley Hall Road Eaton.eu All trademarks are property...
  • Seite 3 Frei programmierbare relaismodule CIOP4, CIOP8 Effective November 2019 Anleitung Elektrische daten: Frei programmierbare relaismodule Buslast CIOP4 und CIOP8 sind soft-adressierbare 4-fach bzw. 8-fach Stromaufnahme Ein-/Ausgangsmodule mit integriertem Kurzschluss-Isolator. Betriebsspannung 18.5V DC 30V DC Sie sind vollständig kompatibel mit dem aktuellen Programm Ausgänge...
  • Seite 4 Verbindung mit der ÜE-Auslösung, gleichgültig welche logische Verknüpfung verwendet wurde. Eaton © 2019 Eaton EMEA Headquarters All Rights Reserved Route de la Longeraie 7 Eaton is a registered trademark. Eaton Electrical Systems Ltd. 1110 Morges, Switzerland Wheatley Hall Road Eaton.eu All trademarks are property Doncaster TEL: +44 (0) 1302 321541 of their respective owners.

Diese Anleitung auch für:

Ciop8