Connections
Site installer operation
1. Run the application Site Installer
2. Select the Graphical Relay Board by right clicking it's
icon, select 'Configure Repeater'
3. Select an output and select 'Add Rule'.
The rules that you can select for the Graphical Relay
Board are: Fire, Fault, Disablement, Test panel, Test zone,
Pre-alarm, FRE, FPE, Reset
Each output on the Graphical Relay Board can have a number of
different rules defined. They are different options which can be
selected for each rule:
Global, By zone, By address, By pane,l By loop, Manual
Example
To select the Graphical Relay Board to respond to a fire
by an address:
1. Select trigger type as fire
2. Select option 'By Address'
3. Select the address to 'respond to'
4. Click OK
Each output on the Graphical Relay Board can have a number of
different rules defined. They are different options which can be
selected for each rule:
Global, By zone, By address, By panel, By loop, Manual
The Graphical Mimic allows additional control so rules can be
evaluated as AND (all rules must be trigger for the output to
trigger) or OR logic (any rules must trigger to activate the output
to activate).
The exception to this rule is FRE input trigger type, which if
added, means regardless of the selected logic, FRE is always
required for the output to activate.
Eaton
EMEA Headquarters
Route de la Longeraie 7
Eaton Electrical Systems Ltd.
1110 Morges, Switzerland
Wheatley Hall Road
Eaton.eu
Doncaster
TEL: +44 (0) 1302 321541
DN2 4NB
FAX: +44 (0) 1302 303220
TEL: +44 (0) 1302 303303
Firesales@eaton.com
FAX: +44 (0) 1302 367155
Firetechsupport@eaton.com
How to use the site installer to download the rules
Graphical Relay Board
Change the jumper on J10 from LOOP to RS232 SETUP
Place a jumper on J2
Connect a serial cable to the Graphical Relay Board
Press the RESET button on the Graphical Relay Board
Site installer
The repeater conguration is not stored on the panel but instead
directly uploaded to the repeater hardware directly. To perform the
upload, right click on the icon in site installer and select 'Upload
Rules to Repeater'. The download from Site Installer
will commence.
Graphical relay board
Remove the serial cable to the Graphical Relay Board
Change the jumper on J10 from RS232 SETUP back to LOOP
Remove the jumper on J2
Press the RESET button on the Graphical Relay Board
Reset the panel that the Graphical Relay Board is connected to
Due to our policy of constant product development we reserve
the right to update specifications at any time without prior notice.
In order to keep you informed we produce Technical Bulletins
detailing changes to specifications or operating procedures for our
product range and how it may affect you. Bulletins will be issued
in response to product upgrades, compatibility changes and useful
engineering feedback. E&OE.
© 2019 Eaton
All Rights Reserved
Eaton is a registered trademark.
All trademarks are property
of their respective owners.
www.Eaton.com
INSTALLATION INSTRUCTIONS 25-16711-A November 2019

Werbung

loading

Diese Anleitung auch für:

Ciop8