Herunterladen Inhalt Inhalt Diese Seite drucken

Prozessdaten Io-Link-Ports, Slot 1.2 - Belden lumberg automation LioN-P PROFINET IO-Link Master S2 Handbuch

Mit profinet-s2-systemredundanz
Inhaltsverzeichnis

Werbung

7.2 Prozessdaten IO-Link-Ports,
Slot 1.2 – 1.9
Bit
Acronym
0
1
2
NewParam
3
SubstDev
4
PortActive
5
DevCom
6
DevErr
7
PQ
Tabelle 35: PQI Beschreibung
106
Short Description
Reserved
Reserved
New parameter
Substitute Device
detection
Port activation
Device communication
Port/Device error
indication
Device Process Data
validity
Handbuch LioN-P PROFINET IO-Link Master S2
Value
Description
0
Reserved
0
Reserved
0
no update of IOL-Device parameter
detected
1
update of IOL-Device parameter
detected: master performed a
parameter storage upload (Master
to Device) and a new IOL-D
Backup object (0xB904) is availbale
0
Not supported, don't evaluate this
bit!
1
Not supported, don't evaluate this
bit!
0
port deactivated via port function
1
port activated (default)
0
no IOL-Device available
1
IOL-Device detected and is in
PREOPERATE or OPERATE state
0
no error/warning occured
1
error/warning assigned to
IOL-Device or IOL-Master port
occured
0
invalid IO process data from
IOL-Device
1
valid IO process data from device