External Voltage Inputs (continued)
Set voltage source to 10 V. Note: the error message SHrt indicates a bad connection.
U=10
Sure
External Current Inputs
Display
Switch on Power, Calibrate link In CAL Position.
u=0
Connect current source and Set to 0 mA.
I=0
Set current source to 20 mA. Note: the error message Open indicates a bad connection.
I=20
Sure
8
QS61001066_Portacal1000_Buch.ind28 28
Ó
Off
Off
On
Ó
I+
I-
V
Keys
Off
Off
On
Ô Õ Ù Ó
On
Off
Off
Ó
Ó
On
Off
Off
Ó
Calibrate 10 V point
To Save Values (or any other key to restart).
Action
Press sequence to select External Voltage
mode. INC and DEC Leds will both light.
Calibrate 0 mA point
Calibrate 20 mA point
To Save Values (or any other key to restart).