Dismounting

4.4

Power supply

Connect the SYMPL Switch to a certified NEC Class 2 24 V DC power
supply unit. To use PoE on any connected device, connect a NEC Class 2
48 V DC power supply unit. Present power supply equates to the status
"On" or running of the SYMPL Node.
To connect the device to a power supply unit, use the provided 2-pole
terminal and lay the wires as stated on the front label. The voltage
assignment is left V+ and right V-.
Turn the power on when all cables are connected to the SYMPL Switch.
When using PoE, the SYMPL Switch is not suited for
!
powering over a DC power supply network. Use the
provided, dedicated power supply unit in the control cabinet
for supplying 48 V DC to the SYMPL Switch.
i
The PoE ports are not galvanically isolated from ethernet
data.
5
Dismounting
Disconnect all attached cables. Dismount the e:cue SYMPL Switch from
the rail by pulling the black DIN rail handle and unhitching the SYMPL
Node. The dismounting is completed.
Before dismounting, appropriate measures must be taken to
!
protect the respective components against damage caused
by electrostatic discharge (ESD protection).
14